Group 98: Options
This group configures for options, in particular, enabling serial communication with the drive.
Table 48: Group 98: Options
Code Description
Range
Resolution
Default
S
9802 COMM PROT SEL
0…5
1
0
Selects the communication protocol .
0 = NOT SEL – No communication protocol selected .
1 = STD MODBUS – The drive communicates with Modbus via the RS485 channel (X1- communications, terminal) .
• See also parameter Group 53 EFB PROTOCOL,
.
2 = N2 – Enables fieldbus communication with the drive using Metasys N2 protocol via the RS485 serial link (X1-communications terminal).
3 = FLN – Enables fieldbus communication with the drive using FLN protocol via the RS485 serial link (X1-communications terminal).
5 = BACNET – Enables fieldbus communication with the drive using BACnet protocol via the RS485 serial link (X1-communications terminal).
Daikin uses the "STD Modbus" selection on all VFDs applied
with MicroTech III controls except for RPE and RDE condenser
fans .
a
CTual
s
Ignals
and
p
arameTers
www .DaikinApplied .com 69
OM 1190-1 • MD4 VFD