Table 74: Parameter Settings
MD4 Parameters
Unit
RoofPak & Self C
Maverick II
Maverick II
RPS / RDT / RCS
RPE / RDE
RoofPak
Maverick II & Rebel
#
Name
SAF, RAF & EAF
SAF
EAF
Condenser Fan
Condenser Fan
Energy Rec Wheel
Energy Rec Wheel
9802
COMM PROT SEL
STD MODBUS
STD MODBUS
STD MODBUS
Not Selected
STD MODBUS
STD MODBUS
STD MODBUS
9901
LANGUAGE
ENGLISH
ENGLISH
ENGLISH
ENGLISH
ENGLISH
ENGLISH
ENGLISH
9902
APPLIC MARCO
HVAC DEFAULT
HVAC DEFAULT HVAC DEFAULT
HVAC DEFAULT
HVAC DEFAULT
HVAC DEFAULT
HVAC DEFAULT
9905
MOTOR NOM VOLT
V
460
460
460
460
460
460
460
9906
MOTOR NOM CURR
A
35
24
4
2 .6
11 .2
1 .1
0 .5
9907
MOTOR NOM FREQ
Hz
60
60
60
60
60
60
60
9908
MOTOR NOM SPEED
rpm
1775
1775
1140
1142
1775
1775
1775
9909
MOTOR NOM POWER
hp
30
20
3
1 .5
5
1
0 .2
1001
EXT1 COMMANDS
COMM
COMM
COMM
DI1
COMM
COMM
COMM
1102
EXT1/EXT2 SEL
EXT1
EXT1
EXT1
EXT1
EXT1
EXT1
EXT1
1103
REF1 SELECT
COMM
COMM
COMM
AI 1
COMM
COMM
COMM
1104
REF1 MIN
Hz
0
0
0
24
0
0
0
1105
REF1 MAX
Hz
60
60
60
60
60
60
60
1106
REF2 SELECT
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
1201
CONST SPEED SEL
NOT SEL
NOT SEL
NOT SEL
DI 3
NOT SEL
NOT SEL
NOT SEL
1601
RUN ENABLE
COMM
COMM
COMM
DI 2
COMM
COMM
COMM
1604
FAULT RESET SEL
COMM
COMM
COMM
KEYPAD
COMM
COMM
COMM
1607
PARAM SAVE
DONE
DONE
DONE
DONE
DONE
DONE
DONE
1608
START ENABLE 1
COMM
COMM
COMM
DI 4
NOT SEL
COMM
COMM
1611
PARAMETER VIEW
LONG VIEW
LONG VIEW
LONG VIEW
LONG VIEW
LONG VIEW
LONG VIEW
LONG VIEW
2101
START FUNCTION
SCAN START
SCAN START
SCAN START
SCAN START
SCAN START
SCAN START
SCAN START
2202
ACCELER TIME 1
s
60
60
60
10
5
60
60
2203
DECELER TIME 1
s
60
60
60
10
30
60
60
2605
U/F RATIO
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
3003
EXTERNAL FAULT 1
DI 2(INV)
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
3009
BREAK POINT FREQ
Hz
45
45
45
45
45
45
45
3101
NUMBER TRIALS
5
5
5
5
5
5
5
3103
DELAY TIME
s
3
3
3
3
3
3
3
3104
AR OVERCURRENT
ENABLE
ENABLE
ENABLE
DISABLE
ENABLE
ENABLE
ENABLE
3404
OUTPUT1 DSP FORM
DIRECT
DIRECT
DIRECT
+0 .0
+0 .0
DIRECT
DIRECT
3405
OUTPUT1 UNIT
%
Hz
Hz
% SP
Hz
Hz
Hz
3415
SIGNAL3 PARAM
AI 1
SPEED
SPEED
AI 1
SPEED
SPEED
SPEED
3418
OUTPUT3 DSP FORM
+0 .0
DIRECT
DIRECT
+0 .0
DIRECT
DIRECT
DIRECT
3421
OUTPUT3 MAX
44ma
1800 rpm
1800 rpm
10v
1800rpm
1800 rpm
1800 rpm
4201
GAIN
The Daikin software version [will grow over time]
4202
INTEGRATION TIME
s
279
252
228
106
103
202
204
5302
EFB STATION ID
SAF=1,R/EAF=2
1
2
1
4
3
3
5303
EFB BAUD RATE
192
192
192
96
192
192
192
5304
EFP PARITY
8 NONE 2
8 NONE 2
8 NONE 2
Values Vary
8 NONE 2
8 NONE 2
8 NONE 2
5306
EFB OK MESSAGES
Usually a big number that continues to grow
5307
EFB CRC ERRORS
0
0
0
0
0
0
0
5308
EFB UART ERRORS
Should be a small number that rarely grows unless a MicroTech III communication problem occurred
5309
EFB STATUS
ON-LINE
ON-LINE
ON-LINE
ON-LINE
ON-LINE
ON-LINE
ON-LINE
8120
INTERLOCKS
NOT SEL
NOT SEL
NOT SEL
DI 4
NOT SEL
NOT SEL
NOT SEL
1002
EXT2 COMMANDS
NOT SEL
NOT SEL
NOT SEL
DI 1
NOT SEL
NOT SEL
NOT SEL
1301
MINIMUM AI1
%
MicroTech III limits minimum speed to 20 hz
10
MicroTech III limits minimum speed to 20 hz
1302
MAXIMUM AI1
%
MicroTech III limits maximum speed to 60 hz
50
MicroTech III limits maximum speed to 60 hz
1303
FILTER AI1
s
0 .1
3502
INPUT SELECTION
A I 1
4210
SET POINT SEL
AI 1
1202
CONST SPEED 1
Hz
60
1401
RELAY OUTPUT 1
FAULT
Vary depending on motor nameplate voltage and hp
These values vary depending on the application
Not important, will be HVAC default values
a
ppendIx
www .DaikinApplied .com 109
OM 1190-1 • MD4 VFD
Содержание ACS320
Страница 115: ......