Specifications
SiUS121827E
34
Part 2 Specifications
1.3 Outdoor Unit
Model
5MXS48TVJU
Cooling
Heating
Power Supply
Phase
1
φ
Hz, V
60 Hz, 208 - 230 V
COP
W/W
—
3.9 (Non-Ducted type connected)
3.2 (Ducted type connected)
EER
Btu/W·h
10.5 (Non-Ducted type connected)
8.6 (Ducted type connected)
—
SEER / HSPF
20.2 (Non-Ducted type connected)
15.3 (Ducted type connected)
11.1 (Non-Ducted type connected)
8.6 (Ducted type connected)
Casing Color
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Model
2YC90KXD
Motor Output
W
3,000
Refrigerant
Oil
Model
FVC50K
Charge
oz (L)
50.2 (1.52)
Refrigerant
Type
R-410A
Charge
Lbs (kg)
8.60 (3.9)
Airflow
Rates
H
cfm
3,684
3,356
M
3,029
3,138
L
2,756
1,500
H
m
3
/min
104.3
95.0
M
85.8
88.9
L
78.0
42.5
Fan
Type
Propeller
Motor Output
W
84
Running Current
A
H: 1.49 / M: 1.09 / L: 0.94
H: 1.28 / M: 1.15 / L: 0.38
Power
Consumption
W
H: 158.5 / M: 93.3 / L: 73.2
H: 122.9 / M: 102.5 / L: 34.9
Starting Current
A
27.0
Dimensions (H × W × D)
In. (mm)
34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460)
Packaged Dimensions (H × W × D)
In. (mm)
39-15/16 × 46-7/8 × 22 (1,014 × 1,190 × 558)
Weight (Mass)
Lbs (kg)
216 (98)
Gross Weight (Gross Mass)
Lbs (kg)
236 (107)
Sound Pressure Level
dB(A)
53
55
Piping
Connection
Liquid
in. (mm)
φ
1/4 × 5 (
φ
6.4 × 5)
Gas
in. (mm)
φ
3/8 × 1,
φ
1/2 × 2,
φ
5/8 × 2 (
φ
9.5 × 1,
φ
12.7 × 2,
φ
15.9 × 2)
Drain
in. (mm)
I.D.
φ
1 (
φ
25)
Heat Insulation
Both Liquid and Gas Pipes
No. of Wiring Connections
3 for Power Supply, 4 for Interunit Wiring
Max. Interunit Piping Length
ft (m)
262 (80) (for Total of Each Room)
ft (m)
98 (30) (for One Room)
Amount of Additional Charge
oz/ft (g/m)
0.21 (20) (131-5/8 ft (40m) or more)
Max. Installation Height Difference
ft (m)
49-1/4 (15) (Between Indoor Unit and Outdoor Unit)
ft (m)
24-5/8 (7.5) (Between Indoor Units)
Conditions based on
Indoor ; 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) / 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) / 60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB) / 43°FWB (6°CWB)
Piping length: 25 ft (7.5 m)
Drawing No.
C: 3D118280
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...