Troubleshooting for Outdoor Unit
SiUS121827E
214
Part 6 Service Diagnosis
7.11 Four Way Valve Abnormality
Error Code
EA
Outdoor Unit LED
Display
A
j
1
i
2
h
3
h
4
h
5
h
Method of Error
Detection
The liquid pipe thermistor and the outdoor heat exchanger thermistor are checked to see if they
function within their normal ranges in the operating mode.
Error Decision
Conditions
The following condition continues for
A
seconds after the compressor has started.
Cooling operation
The lowest liquid pipe temperature among the rooms in operation –Tde > 45°C (113°F)
Heating operation
The highest liquid pipe temperature among the rooms in operation –Tde < 0°C (32°F)
Tde: outdoor heat exchanger temperature
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Cooling
Heating
A
(seconds)
460
1
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...