Troubleshooting for SA Indoor Unit
SiUS121827E
180
Part 6 Service Diagnosis
6.3 Indoor Fan Motor or Related Abnormality
6.3.1 Indoor Fan Motor (DC Motor) or Related Abnormality
Applicable
Models
FDMQ09/12/15/18/24RVJU
Error Code
A6
Method of Error
Detection
Detection from the current flow on the fan PCB
Detection from the rotation speed of the fan motor in operation
Error Decision
Conditions
The rotation speed is less than a certain level for 6 seconds.
Supposed
Causes
Clogged foreign matter
Disconnection of fan motor connectors
Disconnection of the connector between the indoor unit PCB and the fan PCB
Defective fan PCB
Defective fan motor
No fuse continuity
Trouble Shooting
R6000547
Connect the connector
correctly.
Turn OFF the power supply
and wait for 10 minutes.
NO
YES
NO
Connect the connector
correctly.
NO
YES
YES
Replace the fuse.
There is a
continuity in the fuse
(
∗
2) on the fan PCB or fan
motor harness.
NO
The fan motor
connector (
∗
1) is
connected to the fan
PCB.
Remove the foreign matter.
YES
There is a foreign
matter around the fan.
The connector
between the indoor unit
control PCB and the fan
PCB is connected.
A
Go to the next page
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание 4MXL-T Series
Страница 107: ...SiUS121827E SA Indoor Unit Functions Part 4 Functions and Control 101 FFQ Series Emergency operation switch R24077 ...
Страница 182: ...Troubleshooting for RA Indoor Unit SiUS121827E 176 Part 6 Service Diagnosis Reference Check No 11 Refer to P 235 ...
Страница 190: ...Troubleshooting for SA Indoor Unit SiUS121827E 184 Part 6 Service Diagnosis Reference Check No 02 Refer to P 233 ...
Страница 249: ...SiUS121827E Check Part 6 Service Diagnosis 243 R6000583 1 2 3 4 Multimeter Front side Rear side ...
Страница 288: ...Piping Diagrams SiUS121827E 282 Part 8 Appendix 1 2 Outdoor Unit 5MXS48TVJU 4MXL36TVJU 3D117817 3D118311 ...
Страница 298: ...Operation Limit SiUS121827E 292 Part 8 Appendix 4 Operation Limit 5MXS48TVJU 4MXL36TVJU 3D048149D 3D101428 ...