4AMX80E7V3B

R410A Split series

4PW38479-1A

Installation manual

2

If any refrigerant has leaked out during the installation
work, ventilate the room.
The refrigerant produces a toxic gas if exposed to
flames.

After all installation is complete, check to make sure
that no refrigerant is leaking.
The refrigerant produces a toxic gas if exposed to
flames.

When installing or relocating the system, be sure to keep the
refrigerant circuit free from substances other than the specified
refrigerant (R410A), such as air.
Any presence of air or other foreign substance in the refrigerant
circuit causes an abnormal pressure rise or rupture, resulting in
injury.

During pump down operation, stop the compressor before
removing the refrigerant piping.
If the compressor is still running and the stop valve is open
during pump-down, air will be sucked in when the refrigerant
piping is removed, causing abnormal pressure in the freezer
cycle which will lead to breakage and even to injury.

During installation, attach the refrigerant piping securely before
running the compressor.
If the compressor is not attached and the stop valve is open
during pump-down, air will be sucked in when the compressor is
running, causing abnormal pressure in the freezer cycle which
will lead to breakage and even to injury.

Be sure to establish an earth. Do not earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock. A high
surge current from lightning or other sources may
cause damage to the air conditioner.

Be sure to install an earth leakage breaker.
Failure to do so may cause electrical shock.

CAUTION

Do not install the air conditioner in a place where there
is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may
catch fire.

Establish drain piping according to the instructions of this
manual.
Inadequate piping may cause flooding.

Note for installing the outdoor unit. (For heat pump model only.)
In cold areas where the outside air temperature remains below
or around the freezing-point for a few days, the outdoor unit's
drain may freeze. If so, it is recommended to install an electric
heater in order to protect drain from freezing.

Tighten the flare nut according to the specified method such as
with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after
a long time and cause refrigerant leakage.

A

CCESSORIES

Accessories supplied with the outdoor unit:

P

RECAUTIONS

 

FOR

 

SELECTING

 

THE

 

LOCATION

1

Choose a place solid enough to bear the weight and vibration of
the unit, where the operation noise will not be amplified.

2

Choose a location where the hot air discharged from the unit or
the operation noise will not cause a nuisance to the neighbours
of the user.

3

Avoid places near a bedroom and the like, so that the operation
noise will cause no trouble.

4

There must be sufficient space for carrying the unit into and out
of the site.

5

There must be sufficient space for air passage and no
obstructions around the air inlet and the air outlet.

6

The site must be free from the possibility of flammable gas
leakage in a nearby place.

Locate the unit so that the noise and the discharged hot air will
not annoy the neighbours.

7

Install units, power cords and inter-unit cables at least 3 m away
from television and radio sets. This is to prevent interference to
images and sounds.

Depending on radio wave conditions, electromagnetic
interference may still occur even if installed more than 3 m away.

8

In coastal areas or other places with salty atmosphere of sulfate
gas, corrosion may shorten the life of the air conditioner.

9

Since drain flows out of the outdoor unit, do not place anything
under the unit which must be kept away from moisture.

Installation manual

1

Drain socket (A)

1

Drain cap (B)

2

Drain receiver (C)

3

Insulation tape (D)

1

Reducer assembly

1

Make sure to provide adequate measures in order to
prevent that the outdoor unit will be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

NOTE

Units cannot be installed hanging from ceiling or
stacked.

Содержание 4AMX80E7V3B

Страница 1: ...INSTALLATION MANUAL 4AMX80E7V3B R410A Split series ...

Страница 2: ...cm 35 cm 1 2 3 4 7 8 6 15 m 2 15 m 2 7 5 m 1 7 5 m 1 1 2 3 A 1 2 3 4 2 1 L N 5 4 50 Hz 230 V A B 3 C D 1 D C B A 2 S102 S2 S52 A B C D ON SERVICE MONITOR S15 S10 S23 S24 S22 S21 S20 A A H05VV A B C D 3 4 P 1 2 3 4 5 6 7 ...

Страница 3: ...er under forutssetning av at disse brukes i henhold til våre instrukser 13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen että niitä käytetään ohjeidemme mukaisesti 14 za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům 15 u skladu sa slijedećim standardom ima ili drugim normativnim doku...

Страница 4: ... fire Install the air conditioner on a solid base that can support the weight of the unit An inadequate base or incomplete installation may cause injury in the event the unit falls off the base Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete electrical work may cause el...

Страница 5: ...air temperature remains below or around the freezing point for a few days the outdoor unit s drain may freeze If so it is recommended to install an electric heater in order to protect drain from freezing Tighten the flare nut according to the specified method such as with a torque wrench If the flare nut is tightened too hard the flare nut may crack after a long time and cause refrigerant leakage ...

Страница 6: ... remains 20 mm above the foundation surface CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind install a ...

Страница 7: ... figure 3 REFRIGERANT PIPING WORK Installing the outdoor unit When installing the outdoor unit refer to Precautions for selecting the location on page 2 and Indoor outdoor unit installation drawings on page 3 If drain work is necessary follow the procedures below Method for installing drain piping Use drain plug for drainage In cold areas do not use a drain hose with the outdoor unit Otherwise dra...

Страница 8: ...eck for gas leakage from indoor unit s flare and outdoor unit s flare and valve rods After the check is complete wipe all soapy water off 7 Disconnect charging hose from gas stop valve s service port then fully open liquid and gas stop valves Do not attempt to turn valve rod beyond its stop 8 Tighten valve lids and service port caps for the liquid and gas stop valves with a torque wrench at the sp...

Страница 9: ...eat insulation materials that will withstand this temperature Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 Put the flare...

Страница 10: ...ng See figure 5 WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Do never install a drier to this R410A unit in order to guarantee its lifetime The drying material may dissolve and damage the sy...

Страница 11: ...ing electrical shock or fire Do not use locally purchased electrical parts inside the product and do not branch the power for the drain pump etc from the terminal block Doing this may cause electrical shock or fire Be sure to install an earth leakage breaker This unit uses an inverter which means that an earth leakage breaker capable of handling high harmonics needs to be used in order to prevent ...

Страница 12: ...de Night quiet mode function The night quiet mode function reduces operating noise of the outdoor unit at nighttime This function is useful if the customer is worried about the effects of the operating noise on the neighbours Running units in night quiet mode however reduces the cooling heating capacity Setting procedure Remove the SW5 jumper switch Once the settings are complete reset the power C...

Страница 13: ... During the test run first check the operation of each unit individually Then also check the simultaneous operation of all indoor units Check both heating and cooling operation After running the unit for approximately 20 minutes measure the temperatures at the indoor unit inlet and outlet If the measurements are above the values shown in the table below then they are normal During cooling operatio...

Страница 14: ...ctly No cooling no heating Is the wiring in accordance with the specifications Operation failure burning Are the inlets outlets of the indoor and outdoor units free of any obstructions Are the stop valves open No cooling no heating Do the marks match room A room B on the wiring and piping for each indoor unit No cooling no heating Is the priority room setting set for 2 or more rooms The priority r...

Страница 15: ...NOTES NOTES ...

Страница 16: ...4PW38479 1A Copyright Daikin ...

Отзывы: