9
|
Electrical installation
Installer reference guide
54
3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1C – 2020.08
Wire type
Installation method
Stranded conductor wire
with round crimp-style
terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Allowed
NOT allowed
Tightening torques
Item
Tightening torque (N•m)
M4 (X1M)
1.2
M4 (earth)
▪
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
9.1.3 Specifications of standard wiring components
Component
Power supply cable
Voltage
220~240 V
Phase
1~
Frequency
50 Hz
Wire type
A
Interconnection cable (indoor↔outdoor)
4-core cable 1.5 mm
2
or 2.5 mm
2
and applicable for 220~240 V
H05RN-F (60245 IEC 57)
Recommended circuit breaker
B
Earth leakage circuit breaker
MUST comply with applicable
legislation
Model
A
B
3MXM40
3- core cable 2.5 mm
2
H05RN-F (60245 IEC 57)
H07RN-F (60245 IEC 66)
3- core cable 4.0 mm
2
H07RN-F (60245 IEC 66)
16 A
2MXM68,
3AMXM52,
3AMXF52,
3MXF52,
3MXM52,
3MXF68,
3MXM68,
4MXM68
20 A