technical data

Split
Sky Air

air conditioning systems

       

MKS-E2V1B_E7V3B

Multi application

inverter controlled

Содержание 3MKS50E2V1B

Страница 1: ...technical data Split Sky Air air conditioning systems MKS E2V1B_E7V3B Multi application inverter controlled ...

Страница 2: ...data of certified models are listed in the Eurovent Directory The present publication is drawn up by way of informa tion only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this publication to the best of its knowledge No express or implied warranty is given for the complete ness accuracy reliability or fitness for particular purpose o...

Страница 3: ...technical data Split Sky Air air conditioning systems MKS E2V1B_E7V3B Multi application inverter controlled ...

Страница 4: ...ions 6 Electrical Specifications 7 3 Electrical data 8 4 Options 10 5 Capacity tables 11 Combination table 11 Cooling capacity tables 26 6 Dimensional drawing centre of gravity 117 Dimensional drawing 117 Centre of gravity 119 7 Piping diagram 120 8 Wiring diagram 122 Wiring diagram 122 9 Sound data 124 Sound pressure spectrum 124 10 Operation range 125 ...

Страница 5: ...mote control and do not need to be installed in the same room or at the same time They operate simultaneously within the same cooling operation It is possible to combine different types of indoor units as well e g wall mounted ceiling mounted cassette corner concealed ceiling unit Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an ou...

Страница 6: ...tor Model 2YC36BXD 2YC36BXD 2YC63BXD C Type Hermetically sealed swing compressor Motor Output W 1100 1100 1920 Operation Range Cooling Min CDB 10 0 10 0 10 0 Max CDB 46 0 46 0 46 0 Sound Level nominal Cooling Sound Power dBA 59 0 59 0 62 0 Sound Pressure dBA 46 0 46 0 48 0 Sound Level Night quiet Sound Pressure dBA 43 Refrigerant Type R 410A Charge kg 2 0 2 0 3 0 Refrigerant Oil Type FVC50K Charge...

Страница 7: ... relative value depending on the distance and acoustic environment For more details please refer to sound level drawings of this chapter The sound power level is an absolute value indicating the power which a sound source generates 2 2 ELECTRICAL SPECIFICATIONS 3MKS50E2V1B 4MKS58E2V1B 5MKS90E7V3B Power Supply Name V1 V1 V3 Phase 1 1 1 Frequency Hz 50 50 50 Voltage V 220 240 220 240 220 240 Voltage...

Страница 8: ...cal systems where voltage supplied to unit terminals is not below or above listed operation range limits 3 Maximum allowable voltage variation between phases is 2 4 MCA represents maximum input current MFA represents capacity which may accept MCA 5 Select wire size based on the larger value of MCA 6 MFA is used to select the circuit breaker and the ground fault circuit interrupter earth leakage ci...

Страница 9: ...ctrical systems where voltage supplied to unit terminals is not below or above listed operation range limits 3 Maximum allowable voltage variation between phases is 2 4 MCA represents maximum input current MFA represents capacity which may accept MCA 5 Select wire size based on the larger value of MCA 6 MFA is used to select the circuit breaker and the ground fault circuit interrupter earth leakag...

Страница 10: ...1 4 Split Sky Air Outdoor Units 10 Outdoor Units R 410A MKS E2V1B_E7V3B 4 Options 5MKS90E N Item 4MXS80E7 5MXS90E7 5MKS90E7 1 Drain plug KKPJ5F180 4TW27571 1 ...

Страница 11: ...of connected a indoor unit is up to 9 5 kW 3 The above is the value for connecting with the following indoor units 2 0 2 5 3 5 kW class wall mounted D series 3MKS50E Cooling 50Hz 230V Outdoor unit Combination of indoor unit Capacity of each indoor unit Each capacity kW Total capacity kW Total input W Total current A Power factor ARoom BRoom CRoom Rating Min max Rating Min max Rating Min max Rating...

Страница 12: ...W Total capacity kW Total input W Total current A Power factor ARoom BRoom CRoom Rating Min max Rating Min max Rating Min max Rating 3D052267 2 NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature 2 The total ability of connected a indoor unit is up to 10 0 kW 3 The above is the value for connecting with the following indoor units 2 0 2 5 3 5 5 0 kW clas...

Страница 13: ...y kW Total input W Total current A Power factor ARoom BRoom CRoom Rating Min max Rating Min max Rating Min max Rating 3D052267 4 NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature 2 The total ability of connected a indoor unit is up to 10 0 kW 3 The above is the value for connecting with the following indoor units 2 0 2 5 3 5 kW class wall mounted D se...

Страница 14: ...ax Rating Min max Rating Min max Rating 3D052440 2A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 15: ...ax Rating Min max Rating Min max Rating 3D052440 3A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 16: ...ax Rating Min max Rating Min max Rating 3D052440 4A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 17: ...ax Rating Min max Rating Min max Rating 3D052440 5A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 18: ...Rating Min max Rating Min max Rating 3D052441 1A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connecting...

Страница 19: ...ax Rating Min max Rating Min max Rating 3D052441 2A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 20: ...ax Rating Min max Rating Min max Rating 3D052441 3A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 21: ...ax Rating Min max Rating Min max Rating 3D052441 4A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 22: ...ax Rating Min max Rating Min max Rating 3D052442 1A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 23: ...ax Rating Min max Rating Min max Rating 3D052442 2A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 24: ...ax Rating Min max Rating Min max Rating 3D052442 3A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 25: ...ax Rating Min max Rating Min max Rating 3D052442 4A NOTES 1 Cooling capacity is based on 27 CDB 19 CWB indoor temperature 35 CDB outdoor temperature Heating capacity is based on 20 CDB indoor temperature 7 CDB 6 CWB outdoor temperature 2 The total ability of connected a indoor unit is up to 15 6 kW 3 It is impossible to connect the indoor unit for one room only 4 The above is the value for connect...

Страница 26: ...CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052360 1A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted D se...

Страница 27: ...CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052360 1A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted D se...

Страница 28: ... CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052360 2A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted D ser...

Страница 29: ...CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052360 3A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C se...

Страница 30: ...CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052360 3A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C se...

Страница 31: ... CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052360 4A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C ser...

Страница 32: ...B 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 1A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5 5 0kW class wall mounted D ...

Страница 33: ...B 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 1A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5 5 0kW class wall mounted D ...

Страница 34: ...B 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 2A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5 5 0kW class wall mounted D ...

Страница 35: ...B 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 2A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5 5 0kW class wall mounted D ...

Страница 36: ...B 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 3A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5 5 0kW class wall mounted D ...

Страница 37: ...B 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 3A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5 5 0kW class wall mounted D ...

Страница 38: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 4A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C series 5 0kW class ...

Страница 39: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 5A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C series 5 0kW class ...

Страница 40: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 6A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C series 5 0kW class ...

Страница 41: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 6A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C series 5 0kW class ...

Страница 42: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 7A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted D series 5 0kW class ...

Страница 43: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 8A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted D series 5 0kW class ...

Страница 44: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 9A A SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted D series 5 0kW class ...

Страница 45: ...C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052359 9A B SYMBOLS TC Total cooling capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 2 5 3 5kW class wall mounted C series 5 0kW class ...

Страница 46: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 47: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 48: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 49: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 50: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 51: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 52: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 53: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 54: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 5A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 55: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 5A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 56: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 6A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 57: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 6A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 58: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 7A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 59: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 7A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 60: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 8A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 61: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 8A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 62: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 9A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 63: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052449 9A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 64: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052450 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 65: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052450 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 66: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052450 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 67: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052450 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 68: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052450 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 69: ...I TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052450 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTX...

Страница 70: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 71: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 72: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 73: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 74: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 75: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 76: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 77: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 78: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 5A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 79: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 5A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 80: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 6A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 81: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 7A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 82: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 8A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 83: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 8A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 84: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 9A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 85: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052451 9A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 86: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052452 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 87: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052452 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 88: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052452 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 89: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052452 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 90: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052452 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 91: ...C PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052452 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50...

Страница 92: ... PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052452 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20CAVMB 2 5 kW class FTXS25CAVMB 3 5 kW class FTXS35CAVMB 5 0 kW class FTXS50E...

Страница 93: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 94: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 95: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 96: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 97: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 98: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 99: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 5A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 100: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 5A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 101: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 6A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 102: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 6A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 103: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 7A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 104: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 7A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 105: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 8A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 106: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 8A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 107: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 9A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 108: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 9A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 109: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052454 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 110: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052454 1A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 111: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052454 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 112: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052453 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 113: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052454 2A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 114: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052454 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 115: ... TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052454 3A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS...

Страница 116: ...TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 3D052454 4A SYMBOLS TC Total capacity kW PI Power input kW NOTES Capacities are based on following conditions Corresponding refrigerant piping length 7 5 m Level difference 0 m The above is the value for connecting with the following indoor units 2 0 kW class FTXS20D3VMW L 2 5 kW class FTXS25D3VMW L 3 5 kW class FTXS35D3VMW L 5 0 kW class FTXS5...

Страница 117: ... 350 H 1200 600 Installation space for discharge side mm 300 or more room A Gas pipe J9 5 single union Liquid pipe J6 4 single union 3D051793 4MKS58E A Liquid J 6 4 95 Gas J 9 5 85 J 12 7 76 unit mm 2 cuts for anchor bolts Drain outlet I D J15 9 hose for connection Interconnecting piping and wiring inlet 5 Earth terminal Name plate roomC Gas pipe J12 7 single union Liquid pipe J6 4 single union ro...

Страница 118: ...inlet 6 Terminal strip with earth terminal Name plate room A Gas pipe J9 5 single union Liquid pipe J6 4 single union roomB Gas pipe J9 5 single union Liquid pipe J6 4 single union roomC Gas pipe J12 7 single union Liquid pipe J6 4 single union roomD Gas pipe J15 9 single union Liquid pipe J6 4 single union roomE Gas pipe J15 9 single union Liquid pipe J6 4 single union Minimum space for air passa...

Страница 119: ...door Units R 410A MKS E2V1B_E7V3B 1 6 Split Sky Air Outdoor Units 119 6 Dimensional drawing centre of gravity 6 2 Centre of gravity 4D037024J 3MKS50E 4MKS58E 4MKS75E Anchor bolt 4D052060 5MKS90E Anchor bolt ...

Страница 120: ...d pipe thermistor DLC Liquid line stop valve Cooling Header Header Muffler Header Muffler Muffler 3D052057 4MKS58E Heat exchanger RoomA RoomB RoomC Field piping liquid Liquid side Field piping gas Gas side RoomA RoomB RoomC Filter Filter Filter Heat exchanger thermistor DE Electronic expansion valve Electronic expansion valve Electronic expansion valve Filter Outdoor temperature thermistor DOA Pro...

Страница 121: ...n Gas line stop valve Gas pipe thermistor Room A Gas pipe thermistor Room B Gas pipe thermistor Room C Motor operated valve D Discharge pipe thermistor Compressor Accumulator Refrigerant flow Gas pipe thermistor Room D Filter RoomD RoomD Outdoor unit Accumulator DC fan motor Distributor Capillary tube Liquid pipe thermistor Room A Liquid pipe thermistor Room B Liquid pipe thermistor Room C Liquid ...

Страница 122: ...y To indoor unit Room B Room A RoomC RoomA condenser discharge Gas pipe outdoor RoomA RoomC Liquid pipe Indoor Outdoor Sheet metal Room C RoomB RoomB 3D051014 4MKS58E Z1C Z3C Ferrite core X1M X5M Terminal strip Y1E Y4E Electronic expansion valve coil V2 V3 V5 V6 V11 Varistor SA2 Surge arrester FU1 FU2 FU3 Fuse AC1 AC2 U V W X11A E1 E2 HR1 HR2 Connector MRM10 MRM20 MRC W Magnetic relay R1T R11T The...

Страница 123: ...t SW SW2 SW3 Wiring error check SW SW3 SW4 Priority room setting SW SW4 SW5 Night quiet mode setting SW SW5 M1C Compressor motor M1F Fan motor L1R Reactor L Live N Neutral Field wiring Terminal strip Connector Connection Protective earth screw Relay connector Terminal Q1L Overload protector PM Power module PCB1 2 Printed circuit board Y1R Four way valve coil Sheet metal Terminal strip fixed plate ...

Страница 124: ...tion and ambient conditions 3 Reference acoustic pressure 0dB 20μPa 4D052305 Octave band sound pressure level dB 0dB 0 0002 μ bar Octave band center frequency Hz 5MKS90E Cooling approximate threshold hearing for continuous noise NOTES 1 Measured in an anechoic chamber 2 Operation noise differs with operation and ambient conditions 3 The operation noise measuring method is in accordance with JISC96...

Страница 125: ...own period Indoor temp CWB Notes The graph is based on the following conditions 1 Equivalent piping length 7 5 m 2 Level difference 0 m 3 Air flow rate high 4D052044 5MKS90E Outdoor temp CDB Continuous operation Pull down period Indoor temp CWB Notes The graph is based on the following conditions 1 Equivalent piping length 7 5 m 2 Level difference 0 m 3 Air flow rate high ...