Alarms-L
ON
W
ORKS
Two L
ON
W
ORKS
network variables indicate alarm conditions and one network variable clears alarms.
The Chiller Status network output variable indicates that the unit controller is in alarm, but it does not
identify the alarm condition. The Current Alarm network output variable indicates the alarm condition.
Current Alarm
This network output variable indicates the current alarm. The type of alarm is included in the text
string. Alarm messages are listed in Table 9. The unit controller can accommodate 15 simultaneous
alarms. Alarm messages are sent sequentially one every five seconds.
Measurement
Units
Data Type
Valid Range
Default Value
Alarm Message
NA
Structure
0–30 characters plus a NUL
terminator
NA
Variable Details
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoAlarmDescr
Chiller
str_asc
36
31 bytes max