54
ED 15117
signed long
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
149
Present Value
85
Object Name
HeatRecEntWaterTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoEntHRWTemp McQuayChiller
SNVT_temp_p
105
two
bytes
Heat Recovery Leaving Water Temperature
This read only network variable indicates the current temperature of the water leaving the heat recovery
section of the condenser.
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar
signed long
-40°–257°F
-40°–125°C
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
150
Present Value
85
Object Name
HeatRecLvgWaterTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoLvgHRWTemp McQuayChiller SNVT_temp_p
105
two
bytes
Heat Setpoint - Network
This read/write network variable is used to change the Heating setpoint from the network. It sets the
temperature of the Leaving Condenser Water when the chiller is operating in the Heating Mode. The
value is ignored if the unit controller is in cooling mode.
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar
signed long
100.04 to 150.08°F
37.8-65.6°C
134.96°F/57.2°C
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Value
2
6
Present Value
85
Object Name
NetworkHeatTempSetpoint
L
ON
W
ORKS