Figure 5-2
Step 2. Set parameters.
Parameter
Note
Device Name
For recognition only, may be customized.
Device type
As peripheral type supported by current device
,
match device
type in Protocol.
Protocol
One to one match peripheral you will connect
,
protocol name
is the model of protocol. New peripheral shall upload
corresponding protocol referring to Ch 5.9.
Channel type
Physical port connecting the peripheral
Address
Different port type, different address, connection relation is
:
channel type is local switch value
(
Z1~Z16
)
, corresponding
address is 1~16
;
channel type is local analog value
(
A1~A8
)
, corresponding address is 1~8
;
channel type is
serial
(
RS485/RS232 port
),
corresponding address is the
actual COM address of peripheral
;
channel type is network,
address is default.
NO/NC
Channel type is local switch
(
Z1~Z16
)
, need to set NO/NC
according to peripheral type.
Analog Type
Channel type is local analog quantity
(
A1~A8
)
, need to set
current and voltage type according to peripheral type.
Upper Limit
Set according to actual peripheral.
Lower Limit
Set according to actual peripheral.
Compensation
Value
When measure value and actual value differ, you can calibrate
via compensation value.
Chart 5-1
Содержание ARC6416C series
Страница 1: ...1 Video Field Surveillance Unit User s Manual V 1 0 0 For ARC6416C series...
Страница 8: ...Figure 1 1...
Страница 23: ...Figure 4 5 4 3 3 Add Peripheral Protocol Step 1 Click 3 Protocol Management see Figure 4 6...
Страница 76: ...Figure 6 31 Step 2 Click Open See Figure 6 32 Figure 6 32 Step 3 Click Install Certificate See Figure 6 33...
Страница 105: ...Figure 7 3 Click to view detailed alarm of each peripheral see Figure 7 4 Figure 7 4...