Web Manager "Settings" Menu Options
135
Configuring IPDU Power Management
The appropriate value to enter in the “Alarm Threshold” field varies from one
AlterPath PM to the other. The value can be entered either as a number or as a
number with a decimal point, for example, 10 amps or 14.5 amps.
T
To Enable Overcurrent Protection for an
AlterPath PM IPDU
1.
Log into the Web Manager as an administrative user.
2.
Go to Settings
→
IPDU
→
General.
3.
Check “Enable Over Current Protection,” then do the following steps.
a.
Click the “Edit” button next to the IPDU on which you want to set
alarm threshold.
The “Edit Alarm Threshold for IPDU Dialog” appears.
b.
Enter the appropriate number of Amps for the selected type of
AlterPath PM in the “Alarm Threshold” field.
c.
Click OK.
4.
Check “Enable syslog” to enable messages to be sent to the console if the
alarm threshold is exceeded.
5.
Check “Enable buzzer” to cause a buzzer to sound on the PM if the alarm
threshold is exceeded.
6.
Click OK.
7.
Click “Save and apply changes.”
Configuring Users to Manage Power Outlets on a
Connected IPDU
On the Users screen under Settings
→
IPDU, an administrative user can
authorize regular users to manage power outlets. The following figure shows
the screen that displays when a single AlterPath PM is connected to the AUX
port, which has been configured for power management. The list is empty
because no users have yet been configured for power management.
Содержание AlterPath OnBoard
Страница 36: ...xxxvi AlterPath OnBoard Administrator s Guide...
Страница 108: ...Understanding How Configuration Changes Are Handled 72 AlterPath OnBoard Administrator s Guide...
Страница 116: ...Overview of Web Manager Menus 80 AlterPath OnBoard Administrator s Guide...
Страница 146: ...Configuring Regular Users Wizard 110 AlterPath OnBoard Administrator s Guide...
Страница 160: ...Upgrading AlterPath PM IPDU Software 124 AlterPath OnBoard Administrator s Guide...
Страница 194: ...Configuring an Alternate Help File Location 158 AlterPath OnBoard Administrator s Guide...
Страница 292: ...Configuring Private Subnets and Virtual Networks 256 AlterPath OnBoard Administrator s Guide...
Страница 344: ...Using the create_cf Command When Troubleshooting 308 AlterPath OnBoard Administrator s Guide...
Страница 406: ...Understanding Address Configuration for Connected Devices 370 AlterPath OnBoard Administrator s Guide...
Страница 446: ...410 AlterPath OnBoard Administrator s Guide...
Страница 460: ...424 AlterPath OnBoard Administrator s Guide...