![CyberPower RMCARD205 Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/cyberpower/rmcard205/rmcard205_user-manual_2702133048.webp)
CyberPower Remote Management System
46
R
eset to Factory Default Setting / Recover from a Lost Password
To reset the CyberPower Remote Management Card to its factory default setting (including web log-in
user name and password), please following these steps:
RMCARD205
RMCARD305
1. Remove the card from the UPS without turning the UPS/ATS PDU off.
2. Remove the jumper from the reset pins as illustrated. Do not dispose of the jumper.
3. Insert the card into the expansion port on the UPS/ATS PDU.
4. Wait until the green Tx/Rx LED is flashing (the frequency of the ON/OFF flashing is once per second).
5. Remove the card again.
6. Place the jumper back onto the Reset pins.
7. Install card into the expansion port again and tighten the retaining screws.