Professional Tower UPS 

PP800E/PP1100E/PP1500TE 

User Manual 

K01-P1K5000-02

 

SAFETY WARNINGS   

(SAVE THESE INSTRUCTIONS)

 

This manual contains important safety instructions. Please read and follow all instructions carefully 
during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, 
install, or operate your UPS. 
 
This equipment can be operated by any individuals with no previous training. 
 
The socket-outlet shall be installed near the equipment and easily accessible. 
 
During the installation of this equipment it should be assured that the sum of the leakage currents of the 
UPS and the connected loads does not exceed 3.5mA. 
 
Attention, hazardous through electric shock. Also with disconnection of this unit from the mains, 
hazardous voltage still may be accessible through supply from battery. The battery supply should be 
therefore disconnected in the plus and minus pole at the quick connectors of the battery when 
maintenance or service work inside the UPS is necessary. 
 
Do not dispose of batteries in a fire, the battery may explode. 
 
Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes. 

 

 

INSTALLING YOUR UPS SYSTEM   

 
UNPACKING 

 
Inspect the UPS upon receipt. The box should contain the following: 
UPS Unit

¯

1; PowerPanel

®

 Business Edition Software Disk

¯

1; Serial Interface Cable (DB-9)

¯

1; USB 

Device Cable

¯

1;Telephone Cable

¯

1; IEC-IEC Power Cord

¯

4; User Manual

¯

1; PowerPanel

®

 

Business Edition Software User Manual

¯

1. 

 

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 

 

1.  Insure that the equipment plugged into the battery power-supplied outlets does not exceed the UPS 

unit’s rated capacity (800VA/550W for PP800E, 1100VA/700W for PP1100E, 1500VA/1000W for 
PP1500TE). If rated unit capacities are exceeded, an overload condition may occur and cause the 
UPS unit to shut down or the circuit breaker to trip. 

2.  If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert 

Watts (W) or Amps (A) into VA by doing the calculations below. Note: The below equation only 
calculates the maximum amount of VA that the equipment can use, not what is typically used by the 
equipment at any one time. Users should expect usage requirements to be approximately 60% of 
below value. 

 
TO ESTIMATE POWER REQUIREMENTS 

1.              Watts (W) x 2.0 =                    VA or               Amps (A) x 230 =       VA 
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual 

requirements. There are many factors that can affect the amount of power that your computer system 
will require. The total load that you will be placing on the battery-powered outlets should not exceed 
80% of the unit’s capacity. 

 

HARDWARE INSTALLATION GUIDE 

 

1. Connect the equipment to your UPS outlets. The 

IEC-IEC power cords coming with the unit are u
to connect your computer and monitor to the UPS. 

Items such as copiers, laser printers, vacuu
space heaters, or other large electrical d
SHOULD NOT be connected to the UPS.

 Please 

make sure that the total loads of your equipments 
are less than the maximum total power load of yo
UPS. 

sed 

ms, 

evices 

ur 

 

2. Use your computer power cord to connect the UPS 

to a wall outlet. Please avoid using extension cords 
and adapter plugs. (To maintain optimal battery 
charge, leave the UPS plugged in at all times.)

 

 

 
3. Press the UPS power button to turn it on. The “Power On” indicator will be illuminated in “Green”. 
 
4. Install your software and accessories. To use the software, simply use the enclosed serial interface or 

USB cable to connect the UPS unit and your computer. 

 
 

BASIC OPERATION 

 

FRONT PANEL AND REAR PANEL DESCRIPTION 

 
 
 
 

 
 

 

 

 

 

             

   

 

 

 

Power Switch 

 

Press the power button to turn the UPS ON or OFF. 

 

 Power On Indicator 

 
This LED is illuminated when the utility condition is normal and the UPS outlets are 
providing “clean power”, free of surges and spikes. 
 

 

 Using Battery Indicator 

 
This illuminates during utility failure, indicating that the battery is supplying power to the 
battery-power supplied outlets. 
 
 

 

 Boost Indicator 

This LED indicates that the UPS is operating in automatic voltage regulation mode. 
When this indicator is flashing/ illuminated continuously, it indicates that the UPS is 
compensating MAX.14%/ 30% for a low utility voltage.   

 
 

 Buck Indicator 

This LED indicates that the UPS is operating in automatic voltage regulation mode. 
When this indicator is illuminated continuously, it indicates that the UPS is 
compensating MAX.12% for a high utility voltage.   
 
 

 Battery Backup and Surge Protection Outlets

   

 

The UPS provides battery 4 powered and surge protected outlets for 
connected equipment to insure temporary uninterrupted operation during a 
power failure and against surges and spikes. 

 

 

 

 

 

 

 Surge Protection Outlets 

 
 

The UPS provides 2 surge protected only outlets for connected equipments 
against surges and spikes. 

 

 

 

 

 

 

 

 Serial/USB Port to PC 

 

This port allows connection and

 

communication from the DB-9 serial or USB port on the 

computer to the UPS unit. The UPS communicates its status to the PowerPanel

®

       

Business Edition software. This interface is also compatible with the UPS service 
provided by 

Windows 98, Windows ME, Windows NT, Windows 2000, Windows XP, 

Windows Server 2003. 
 
 
 

NOTE: 

Only one of these two ports can be used as communication and control of the UPS unit at one 

time. 

 

 Ethernet (RJ-45) Network Protection Ports 

 

 

 

 

These ports are the protection for your computer network device. 
 

 

 

BATTERY REPLACEMENT AND STORAGE 

 
CAUTION!

 Read and follow the 

IMPORTANT SAFETY INSTRUCTIONS 

before servicing the battery.   

Service the battery under the supervision of personnel knowledgeable of batteries and their 
precautions. Keep unauthorized personnel away from batteries. 

If you have questions, 

contact 

your dealer or call the number in this manual

 for information on battery replacement. 

CAUTION! Use only the specified type of battery. 

See your dealer for replacement batteries. 

CAUTION!

 The battery may present the risk of electrical shock. 

Do not dispose of batteries in a fire

as it may explode. Follow all local ordinances regarding proper disposal of batteries. 

CAUTION! 

Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and 

may be toxic. 

CAUTION! 

A battery can present a high risk of short circuit current and electrical shock. 

Take the 

following precautions before replacing the battery

 
1. Remove all watches, rings or other metal objects. 
2. Only use tools with insulated handles. 
3. 

DO NOT 

lay tools or other metal parts on top of battery or any battery terminals. 

4. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of 

ground. 

CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK! 

The likelihood of such shock will be reduced if such grounds are removed during installation and 
maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit). 

5. Batteries are consider 

HAZARDOUS WASTE

 and must be disposed of properly. Contact your local 

government for more information about proper disposal and recycling of batteries. 

6. Turn off and unplug all connected equipment. 
7

urn the UPS off and unplug it from the AC power source. 

. T

8

Turn the UPS upside down. 

 
 

 