User Manual 29 / 43 CPS Mini Central series
7.
Start-Up and Shut down the inverter
Make sure the inverter has connected DC and AC conductor cables
correctly according to the wiring diagram of section 6.1
&
6.2.
Always make sure the maximum open circuit voltage (Voc) of each PV
string is less than 1000VDC.
7.1
Start-Up the inverter
Turn on the DC switch of the inverter, and the inverter will start automatically when the
input voltage is higher than 200V.
The LCD display shown the information as below picture in the initialized stage:
Fig 7.1
The display following shown the information below and the LED will turn to red without
utility:
Fig 7.2
In order to connect to AC grid you must turn on AC disconnect
The LCD text line's information display as below:
Fig 7.2
When timer counts to 0s, the inverter attempts to connect to the grid. Once it outputs
power to the grid successfully, LCD shown as below picture and LED turn to green.
Fig 7.3
It means the CPS Mini Central inverters successfully start up!