WARNING
If the ground wiring was not done correctly, thunderstorms can destroy the EDGE
Bin Scale
NOTICE
When tightening the Earth terminal blocks inside the EDGE Bin Scale, use a torque
from 7.9lbf*in (0.9N*m) to 8.9lbf*in (1.0 N*m) to fasten a wire gauge from 14AWG
(diameter of 1.62mm or cross sectional area of 2.08mm
2
) to 16AWG (diameter of
1.29mm or cross sectional area of 1.30mm
2
).
WARNING
If metal rigid tubes are used, ensure they are correctly grounded.
WARNING
Installation must only be performed by qualified service personnel.
Wiring Connections
The power and communications wires between the
EDGE Controller
and the
Bin Scale 3 Wires LC
must
be connected so they can relay information.
WARNING
Disconnect power before servicing.
Wiring guidelines
• Bin scale module must be closed of a 3/6–slot; see table below for appropriate wire size.
• The entire communications network must not exceed the length listed for the wire gage to work
properly.
• The shield wire for the power and connection wires must be connected to EARTH at one end of the
cable.
• It is recommended to use different pathways for the Automation & Safety cables.
• First twisted pair (blue & white) must be used for A and B wires and a second twisted pair (black &
red) must be used for 24V and GND.
Table 3-1
Power Cable Options (24V and GND)
Distance
Minimum wire gage
Minimum diameter
Minimum cross section
150 m (500 ft)
18 AWG
1.02 mm
0.82 mm
2
300 m (1000 ft)
16 AWG*
1.29 mm
1.30 mm
2
600 m (2000 ft)
14 AWG
1.62 mm
2.08 mm
2
900 m (3000 ft)
12 AWG
2.05 mm
3.30 mm
2
1200 m (4000 ft)
10 AWG
2.58 mm
5.26 mm
2
* Recommended
32
891–00577
EDGE Bin Scale 3 Wires LC
Содержание 074-11772
Страница 1: ...EDGE Bin Scale 3 Wires LC Models 074 11773 Owner s manual 891 00577 Version 01 Date 02 27 18 891 00577...
Страница 26: ...NOTES 26 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 34: ...Chapter 3 Basic connections Figure 3 3 Loadcell Wiring 34 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 38: ...NOTES 38 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 48: ...Chapter 6 Setup Figure 6 2 Tank group setup screen 48 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 50: ...Chapter 6 Setup Figure 6 3 Out of feed alarm setup screen 50 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 59: ...891 00577 EDGE Bin Scale 3 Wires LC 59...
Страница 64: ...NOTES 64 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 66: ...NOTES 66 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 68: ...NOTES 68 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 78: ...NOTES 78 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 80: ...NOTES 80 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 82: ...NOTES 82 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 84: ...NOTES 84 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 88: ...NOTES 88 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 90: ...NOTES 90 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 94: ...NOTES 94 891 00577 EDGE Bin Scale 3 Wires LC...
Страница 100: ...NOTES 100 891 00577 EDGE Bin Scale 3 Wires LC...