I/STAT-LCD 

Installation Sheet

Overview

The I/STAT-LCD is similar to CSI’s standard 
I/STAT, except for the following differences:

The LED display has been replaced with 
an LCD display.

The three electrical leads have been 
replaced with a single terminal block.

The I/STAT-LCD and standard I/STAT oper-
ate identically. However, the installation pro-
cedures for the I/STAT-LCD are unique. 
Therefore, use the instructions within this 
Installation Sheet to mount the I/STAT-LCD 
to a surface, and to connect it to a controller 
(i.e, an MR, ASC, 7728, or NetPoint device). 
For all other purposes (i.e., controlling a 
point, displaying a point value, etc.), use the 
standard I/STAT instructions within your 
I/NET documentation.

troller to TB1 terminal 1 on the 
I/STAT-LCD.

Note:

If the DATA wire is not properly con-
nected to terminal 1, the I/STAT-LCD 
will display a flashing “CSI”.

b. Connect the +12 VDC POWER wire 

from the controller to TB1 terminal 2 
on the I/STAT-LCD.

c. Connect the GROUND wire from the 

controller to TB1 terminal 3 on the 
I/STAT-LCD.

Note:

When using shielded cable, the grounded 
drain/shield wire may be used to connect 
GROUND to TB1 terminal 3 on the 
I/STAT-LCD.

4. Reconnect power to the controller that is 

connected to the I/STAT-LCD.

5. Program the I/STAT-LCD from the host 

workstation (details in the I/NET Opera-
tor Guide).

Front

Back

TCON286 – 10/00