Electrical wiring
VA 525 EN V1.01
Page 12 of 41
9
Electrical wiring
9.1
Modbus RTU, 4…20mA, Pulse, MBus or Ethernet
Attention:
Not required connections NC must not be connected to a voltage and/or to protection
earth. Cut and insulate cables.
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Connector plug
A
Version Modbus
+VB
RS 485 (A)
-VB
RS 485 (B)
NC
Connector plug
A
(Version 4..20mA)
+VB
Pulse
galv. isolated
-VB
Pulse
galv. isolated
I+
4..20 mA
Connector plug
A
Version MBus
+VB
NC
-VB
MBus
MBus
Colours cables
0553 0106 (5 m)
0553.0107 (10 m)
brown
white
blue
black
grey
Legend:
-VB
Negative supply voltage 0 V
Pulse
Pulse for consumption
+VB
Positive supply voltage 18...36 VDC
smoothed
NC
Must not be connected to a voltage
and/or to protection earth. Please cut
and isolate cables.
I +
Current signal 4...20 mA
(selected measured signal)
RS 485 (A)
RS 485 (B)
Modbus RTU A
Modbus RTU B
MBus
MBus (reverse polarity protected)
If no connection cable cable is
ordered the sensor will be
supplied with a M12 connector
plug. The user can connect the
supply and signal cables as
indicated in the connection
diagram.
.
M12 Connector plug
View from back side
(terminal side)
Connection plug A
Connection plug B
(OptionEthernet)