29
TABLE 11.0b: CARLIN BURNER CONFIGURATION AND SETUP DATA
BURNER MODEL
EZ-1HP
EZ-1HP
EZ-1HP
EZ-1HP
EZ-1HP
EZ-1HP
EZ-1HP
EZ-2HP
STANDARD
DEL.
HAGO
HAGO
DEL.
DEL.
HAGO
HAGO
DEL.
NOZZLE
0.55/70B 0.60/60ES 0.85/60B 0.75/60A 1.00/60A 1.25/60B 1.00/60B
1.50/60A
PUMP PRESS (psi)
150
150
150
150
150
150
150
150
HEAD BAR
0.50
0.60-0.65 0.85-1.00
0.75
0.85-1.00 1.10-1.25 0.85-1.00
1.50
STARTING
BAND SETTING
0.55
0.60
0.75
0.75
1.00-1.10 1.25-1.35
0.90
1.75
DRAFT OVER FIRE
(in w.c.)
MAX. SMOKE
(bacharach scale)
FLUE CO2 (%)
MIN.
11.0
11.0
11.0
11.0
11.0
11.0
11.0
11.0
MAX
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
TWZ125 TWZ150 TWZ120 TWZ175 TWZ200
-0.02
-0.02
-0.02
-0.02
BOILER MODEL
TWZ065 TWZ075 TWZ100 TWZ090
#1
#1
#1
-0.02
-0.02
-0.02
-0.02
#1
#1
#1
#1
#1
TABLE 11.0c: RIELLO BURNER CONFIGURATION AND SETUP DATA
BURNER MODEL
40F5
40F5
40F5
40F10
40F10
40F10
STANDARD
DEL
DEL
DEL.
DEL
HAGO
DEL
NOZZLE
0.60/60A 0.85/60W
1.00/60A 1.25/60B
1.35/45B 1.65/45B
PUMP PRESS (psi)
150
150
150
150
150
150
TURBULATOR
0
2
4
1
1.5
2
AIR
SHUTTER SETTING
2.60
2.85
4
3
3
3.8
DRAFT OVER FIRE
(in w.c.)
MAX. SMOKE
(bacharach scale)
FLUE CO2 (%)
MIN.
11.0
11.0
11.0
11.0
11.0
11.0
MAX
12.5
12.5
12.5
12.5
12.5
12.5
TWZ150
TWZ120
TWZ175
TWZ200
BOILER MODEL
TWZ065
TWZ075
TWZ100
TWZ090
TWZ125
-0.02
#1
#1
#1
#1
#1
#1
-0.02
-0.02
-0.02
-0.02
-0.02
Содержание TWZ Series
Страница 2: ......
Страница 10: ...8 FIGURE 4 1 INSTALLATION OVER A COMBUSTIBLE FLOOR FIGURE 4 0 CLEARANCES...
Страница 27: ...25 FIGURE 10 0 CONNECTIONS DIAGRAM BOILERS WITH OR LESS TANKLESS HEATER...
Страница 28: ...26 FIGURE 10 1 CONNECTIONS DIAGRAM FOR BURNER PRIMARY CONTROLS Carlin 40200 Beckett 7505 Riello 530SE...
Страница 47: ...45...
Страница 49: ...47...
Страница 50: ...48 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 51: ...49 Notes...