Alarm to Output
Parameter
Description
Default Configuration
Alarm from zones
If an Area is Armed and a zone assigned to that Area activates,
the zone can trigger selected Outputs for local alarm signaling.
This location assigns Zones to Outputs for alarms that occur
when in the Full Armed State
No Outputs selected
Stay Alarm from zones
If an Area has Stay Mode Armed and a zone assigned to that
Area activates, the zone can trigger selected Outputs for local
alarm signaling. This location assigns Zones to Outputs for
alarms that occur when Stay Mode is Armed
No Outputs selected
24H Alarm from zones
If a zone is programmed as one of 24 Hour type zone and if it is
open then the selected output(s) is activated for local alarm
signaling. In case of standard 24-hour zone the output will be
active for the full reset time. In case of 24-hour auto-reset zone
the output is deactivated when the reset time expires or if the
zone is closed. If a zone is a 24-hour fire zone then the output
will pulse at a rate equals to the pulse time for that output.
No Outputs selected
Alarm to Outputs
(cont)
Parameter
Description
Default Configuration
Tamper from zones
Zone tamper can trigger selected output(s) for
local alarm signaling.
No Outputs selected
Chime alarm from zones
If a zone is programmed as a Chime zone and it
activates, the zone can trigger selected Outputs
for local alarm signaling. The output will operate
for the Chime to Output time at location. The zone
must clear before the output can be activated
again
No Outputs selected
Entry delay from armed zones
If the panel is Armed and a delay zone triggers, the
entry delay it can also turn an Output to ON to
warn that the entry delay is counting down and
the alarm should be turned off
No Outputs selected
Stay entry delay from zones
If Stay Mode is Armed and a delay zone triggers
the entry delay it can also turn an Output to ON to
warn that the entry delay is counting down and
the alarm should be turned off
No Outputs selected
Near Alarm from zones
If zones are programmed for near and verified
alarms, it is also possible to get an indication of a
near alarm from any of the 16 outputs using this
program location. A near alarm is the first alarm
during an armed period
No Outputs selected
verified alarm from zones
If zones are programmed for near and verified
alarms, it is also possible to get an indication of a
verified alarm from any of the 16 outputs using
this program location. A verified alarm is the
second alarm from a different zone to the one that
caused the near alarm and must happen within 45
minutes of the near alarm
No Outputs selected