![CROW ELECTRONIC ENGINEERING LTD. GBD-PLUS Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/crow-electronic-engineering-ltd/gbd-plus/gbd-plus_installation-instructions_2689406001.webp)
1 2 3
GBD-PLUS
COMPACT
GLASS BREAK DETECTOR
ELECTRONIC ENGINEERING LTD.
INSTALLATION INSTRUCTIONS
P/N 7101352
Ver. G A.Y.
The GBD-PLUS is the ultimate answer for all
those tired of false alarms. It listens for
sounds of breaking glass, which produce two
sequential signals of different frequencies.
The unique phased frequency detection
circuitry of this detector allows detection of
both shock signal and the strong signal of
glass breakage creating a “false alarm free”
glass break detector.
The detector does not need to be attached to
the window, providing volume protection, and
allowing you to protect several windows with
one detector.
FEATURES
•
Shock and/or breakage selectable
•
Analyzes two frequencies
•
Unique signal analysis ignores
environmental disturbances
•
Memory LED
•
Sensitivity adjustment
•
New ultra compact design
•
Flush mount installation (option)
•
Outstanding detection range and reliability
FIG. 1 - MOUNTING
The detector offers flexible installation. It can
be either ceiling mounted or wall mounted as
shown in the figure above.
4 5 6
MOUNTING LOCATION ( See FIG. 1 )
•
If heavy blinds or curtains cover the glass,
you must locate the detector behind the
blinds on the window frame or above it,
otherwise the blinds might block the
sound. Make sure to test the unit
thoroughly for proper detection.
•
Install the detector in a direct line of sight
with the protected glass.
•
Do not mount the unit in front of air ducts,
or close to bells (measuring 0.5m (or
larger) in diameter).
•
For a few protected glasses in one room,
locate the detector in optimal distance
from them to achieve the best detection.
Note:
for symmetrical cover of the detection
area it is recommended to place the
detector on the ceiling.
MOUNTING THE DETECTOR ( FIG. 2 )
1.
Use a small screwdriver to push the prong
on top of the case and open the case.
2.
Snap out the detector PCB.
3.
Insert the wires through the wiring hole (B).
4.
Use the mounting holes (A) to mount the
detector.
5.
Connect the wires to the terminal.(See
Terminal Connections)
6.
Reinstall the detector PCB.
7.
Close the case.
JUMPERS ( FIG. 4 )
•
JP1
- Shock / Glass selector for detection
calibration.
•
JP2
– Memory LED control.
•
JP3
- Reduces the sensitivity of sound
detection by 50%.
FIG. 2 - THE BACK COVER
A
A
B
7 8 9
FIG. 3 - TERMINAL BLOCK
TERMINAL BLOCK CONNECTIONS
Terminal 1 - Marked - ( GND )
Connect to ground of the control panel.
Terminal 2 - Marked + ( +12V )
Connect to the positive Voltage output of 9-16
Vdc
source (usually from the alarm control unit)
Terminals 3 & 4 - Marked TAMPER
If a Tamper function is required connect these
terminals to a 24hour normally closed protective zone
in the control unit. If the front cover of the detector is
opened, an immediate alarm signal will be sent to the
control unit.
Terminals 5 & 6 - Marked RELAY
These are the output relay contacts of the detector.
Connect to the control at zone input.
THE CALIBRATION TOOL ( * )
The Simulator/Tester & Calibration tool is
especially designed to check phased
frequency glass break detectors.
Since the detector will react to the high
frequency breakage sound only when it
comes sequentially after a low frequency
SHOCK sound, this device is necessary to
check for proper operation of the GBD-PLUS
without actually breaking the glass.
Manual mode
:
In this mode, the Simulator will emit the high
frequency sound of breaking glass for "Glass"
adjustment.
Automatic mode
:
In order to simulate breaking glass, place the
Simulator on the surface of the protected
glass, and gently hit it with your hand. The
Simulator will then emit the sound of breaking
glass. Be careful not to break the glass while
testing the detector.
∗
It is recommended to use
simulator
CROW
P/N: 0040011
TESTING THE DETECTOR
First use the Simulator in manual mode to
simulate the noise of glass breaking. Check
that the yellow LED is ON. If it does not light,
the sensitivity calibration is necessary (See
Sound Calibration).
Now use your hand or a padded object to
carefully strike the glass. If the green LED
does not light, adjust as necessary (See
Shock Calibration).
Now use the Simulator in automatic mode
and check that the red LED lights. If the red
LED is ON, your detector is working properly.
Otherwise try adjusting the sound and shock
setting until the red LED lights.
N345