41
3.3.10
Programming field 9 : select size of battery bank
This function enables to adjust BOOST trimming versus size of battery bank
Setting
Factor of multiplication of BOOST trimming
1
1
2
1.5
3
2
4
2.5
5
3
3.3.11
Programming field 10 : select CAN protocol
This function enables to change CAN protocol
Setting
CAN-Bus protocol
1
Protocol Cristec
2
Protocol SH
3
Protocol PH
4
Protocol J1939
3.3.12
Thermal compensation
STP-UNI-2.8 and STP-UNI-5.0 temperature probes enable the compensation of Absorption voltage and Floating Voltage
depending on the ambient temperature of the battery room.
The coefficient used is -18mV/°C for 12V model and -36mV/°C for 24V models.
Temperature is not compensated when wintering (or standby sealed bat),
stabilized DC power supply and lithium iron phosphate (LiFePO4)
with BMS settings are selected.
Option not compatible with option alternator protection.
3.3.13
Alternator protection
STP-ALT-2.4 temperature probes enable the protection of the alternator
from a
temperature too high.
Option not compatible with option thermal compensation.