Product Manual — Doc. 7389C
GL-IPAC-SW8 • 24
Set External Load IDs
Each load in an external panel is controlled by a lighting module. To properly control the external
loads in a system, the connected modules must be identified to the GL-IPAC-SW8.
To identify the connected modules:
1. Set the ID of an external module according to the list on the right side of the screen.
2. Press OK to exit the screen.
NOTE: ERR indicates that a module ID cannot be found.
Set Module ID Screen
Occupancy Sensors
Occupancy Sensors configures internal, Cresnet, and GLS-SIM occupancy sensors connected to
the GL-IPAC-SW8.
To configure occupancy sensors:
1. Select Occupancy Sensors from the Setup menu. The Occ Sensr List screen provides a list
of all connected occupancy sensors. There can be a total of 24 occupancy sensors
connected to the GL-IPAC-SW8. There are three types of occupancy sensors:
l
4 internal, non-system sensors (Sensor 1 to 4)
l
10 external Cresnet sensors (Sensors B0.1 to B9.1)
l
10 external, non-system sensors connected to Cresnet via GLS-SIM (Sensors C0.1 to
C9.1)
2. Configure the desired occupancy sensor as described in the following sections.
Press Exit to return to the Setup menu.
Occ Sensr List Screen