background image

DO

 

GUIDE

Observe the following when connecting the CP3-R:

 

Use Crestron power supplies for Crestron equipment.

 

The CP3-R may be powered with the included 24 Vdc power supply or with the NET 4-pin terminal block connector.

 

The included cables may not be extended.

 

Connect the chassis ground lug to a known earth ground circuit to ensure the CP3-R is properly grounded (for example, building steel). 

 

Apply power after all connections have been made. 

DO

 Download the Crestron Pyng

®

 App

The Crestron Pyng

®

 app may be downloaded onto an Apple

®

 iPad

®

 device from the iTunes

®

 application App Store

®

 online store.

NOTES:

 

 

An iTunes account is required to download the Crestron Pyng app. Refer to 

https://support.apple.com/kb/HT2731

 for help with setting up an iTunes 

account.

 

For a comprehensive list of iOS

®

 hardware and software versions that are compatible with the Crestron Pyng app, refer to OLH article 5655 at  

https://support.crestron.com/app/answers/detail/a_id/5655

.

To download the Crestron Pyng app:

1.  Tap the 

App Store 

icon       on the iPad device home screen.

2.  Tap the search field, and enter the search term “Crestron Pyng.”

3.  Tap 

Search

.

4.  Tap the 

Crestron Pyng 

app icon      .

5.  Follow the prompts to download the app to the device.

DO

 Configure the System

Once the Crestron Pyng app is downloaded and installed, system setup takes place entirely through the app.

Tap the Crestron Pyng app icon       on the iPad device home screen. The Crestron Pyng app connects to the CP3-R automatically, and a splash screen is 
displayed. 

NOTE:

 Ensure that the iPad device and the CP3-R are placed on the same subnet prior to configuration.

For more information on setting up and configuring the Crestron Pyng system, refer to the Crestron Pyng Application for CP3-R Product Manual (Doc. 8356) 
a

www.crestron.com/manuals

.

CP3-R

 

3-Series

®

 Control Processor for Crestron Pyng

®

 Application

DO

 Install the Device

The Crestron

®

 CP3-R may be mounted into a rack or placed onto a flat surface. 

Mount into a Rack

The CP3-R occupies 1U of rack space. Use a #1 Phillips screwdriver to remove the required screws from the CP3-R assembly (shown in the illustration 
below), and then attach the two included rack ears with the removed screws. Mount the CP3-R into the rack with four mounting screws (not included).

Place onto a Flat Surface

When the CP3-R is placed onto a flat surface or stacked with other equipment, attach the four included feet near the corners on the underside of the CP3-R.

DO

 Connect the Device

Make all necessary connections to the CP3-R as shown in the illustration below. 

NOTE:

 Ensure that the included SD card is seated fully in the MEMORY slot prior to powering on the CP3-R.

DO

 Check the Box

QUANTITY

ITEM

PART NUMBER

2

Bracket, Rack Ear, 1U

2032122

1

Cable, USB 2.0, A - B, 6’ (1.83 m)

2014966

2

Connector, 3-Pin

2003575

1

Connector, 4-Pin

2003576

1

Connector, 5-Pin

2003577

4

Connector, 8-Pin

2003580

1

Connector, 9-Pin

2003581

4

Foot, 0.5" x 0.5" x 0.23", Rubber, Black

2002389

4

IR Emitter Probe, with Terminal Block Connector, IRP2

4500152

1

Power Cord, 5' 10" (1.78 m)

2042043

1

Power Pack, 24 Vdc. 2.5 A, 100-240 Vac

2045873

PORT RS-232

RS-422

1

RS-485

G

GND

GND

GND

2

TX

TX (from CP3-R)

TX- (from CP3-R)

TX-/RX-

RX

RX (to CP3-R)

RX+ (to CP3-R)

Not Used

RTS RTS (from CP3-R)

TX+ (from CP3-R)

TX+/RX+

CTS CTS (to CP3-R)

RX- (to CP3-R)

Not Used

COM 1 Connections

1

 RS-422 transmit and receive are balanced signals that require two lines plus a ground in each 

  direction. RXD+ and TXD+ should idle high (going low at start of data transmission). RXD- and 

  TXD- should idle low (going high at start of data transmission). If necessary, RXD+/RXD- and 

  TXD+/TXD- may be swapped to maintain correct signal levels. 

2

 A ground terminal connection is recommended but not required.

USB

LAN

G

TX

RX

G

COM2

COM1

COM3

TX

RX

G

RTS

TX

RX

CTS

G

24 Y Z G

NET

1 2 3 4 5 6 7 8 G

I/O

1

2

3

4

5

6

7

8

RELAY OUTPUT

S

1

2

3

4

G S G S G S G

S

5

6

7

8

G S G S G S G

IR - SERIAL OUTPUT

2.0A

24V

---

CONTACTS DOWN

MEMORY

MAC ID LABEL

SERIAL LABEL

24W MAX. CLASS 2

RELAY OUTPUT (1–8):

To contact closure

devices

I/0 (1–8):

To controllable

devices

IR - SERIAL (1–8):

To TLL/RS-232

devices

COM1:

To serial 

controlled

devices

COM2/COM3:

To serial

controlled

devices

MEMORY:

SD-compatible 

card slot

USB:

To storage

devices

LAN:

10BASE-T / 

100BASE-TX

Ethernet to LAN

NET:

To any Cresnet

®

network device

24V, 2.0A:

From ac

power pack

Ground

Отзывы: