Страница 2: ...by the Technical Documentation department at Crestron Electronics Inc 15 Volvo Drive Rockleigh NJ 07647 1 888 CRESTRON All brand names product names and trademarks are the property of their respectiv...

Страница 3: ...26 Setpoints 26 Hold 26 Remote Operation 27 LCD Display 28 Programming Software 30 Earliest Version Software Requirements for the PC 30 Programming with Crestron D3 Pro or SystemBuilder 30 Programming...

Страница 4: ......

Страница 5: ...this guide these thermostats are referred to as CHV TSTATRF The features and specifications for all three thermostats are identical Features and Functions Wall mounted heat cool thermostat For baseboa...

Страница 6: ...touchpanels keypads wireless remotes and computers to support unlimited flexibility for remote control scheduling and integration with other devices and systems However in the event that communicatio...

Страница 7: ...ter function and value Measurement Range Ambient Temperature 10 to 110 F 23 to 43 C Display Limits 9 to 99 F 9 to 43 C Setpoint Range Heat only setpoint 38 to 89 F 3 to 32 C Cool only setpoint 59 to 9...

Страница 8: ...ese footnotes 2 Crestron 2 Series control systems include the AV2 and PRO2 Consult the latest Crestron Product Catalog for a complete list of 2 Series control systems NOTE Crestron software and any fi...

Страница 9: ...STATRF Overall Dimensions Front and Side Views 1 03 in 2 60 cm 5 53 in 14 05 cm 4 50 in 11 43 cm 1 2 3 4 5 MODE FAN CHV TSTATRF Overall Dimensions Rear View 3 27 in 8 30 cm Operations Installation Gui...

Страница 10: ...setting call activity low battery RF or control system communication errors firmware download progress setup parameter function and value 6 HVAC 4 Two position terminal blocks C 24 VAC common termina...

Страница 11: ...ere is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning...

Страница 12: ...t plate from back plate you may need to exert force when removing the front plate 2 Turn HVAC system power OFF 3 Feed HVAC wiring from the electrical box through the hole in the center of the back pla...

Страница 13: ...Crestron CHV TSTATRF infiNET Thermostat Installation view Operations Installation Guide DOC 6490A infiNET Thermostat CHV TSTATRF 9...

Страница 14: ...HV TSTATRF RH Reference Heat Used for calls to the heating system RC Reference Cool Used for calls to the cooling system G Fan Switched to RC during call for fan Y Compressor Switched to RC when compr...

Страница 15: ...n Application Transformer Heat Relay Optional for power R C System 120 VAC Fan Relay RH RC jumper required since supply power is returned through RH Refer to Basic Thermostat Setup on page 15 NOTE To...

Страница 16: ...Relay Fan Relay RH RC jumper required since supply power is returned through RH CHV TSTATRF in Heat Cool Application with Separate Systems C W R Y R Compressor Relay Transformer R C Cooling Transform...

Страница 17: ...inal Optional for power Transformer R C C Y G O E U W R Compressor Relay Fan Relay Changeover Valve Aux Heat Relay Refer to Basic Thermostat Setup on page 15 NOTE Heat pump and dual fuel heat pump sys...

Страница 18: ...Compressor Relay Fan Relay Changeover Valve Transformer R C Optional for power Fossil Heat System Refer to Basic Thermostat Setup on page 15 NOTE The diagram above applies where furnace control is no...

Страница 19: ...lways available 24 and steal power SP By default the CHV TSTATRF is configured to be powered by two AA alkaline batteries In addition in order to extend battery life the device is able to steal power...

Страница 20: ...ET Setup The MNET ID of the CHV TSTATRF has been factory set to 01 After an infiNET device is added to an infiNET network its MNET ID must be changed to a value that can be addressed by the control sy...

Страница 21: ...start the acquire process display shows flashing in progress When finished display shows 00 finished found gateway or E finished could not find gateway where represents an error code NOTE The acquire...

Страница 22: ...ensure that a CHV TSTATRF has been added at the proper MNET ID Refer to Programming with Crestron D3 Pro or SystemBuilder on page 30 or Programming with SIMPL Windows which starts on page 30 Four bri...

Страница 23: ...the MODE button for more than one second will reset the currently selected parameter function to its default value When setting parameters such as when choosing between Fahrenheit or Celsius display...

Страница 24: ...dF HC Sets the system type being used Heat pump type will allow aux heat to stage with the heat pump A dual fuel heat pump type will not allow both systems to run at the same time Auto mode AU Disable...

Страница 25: ...systems Ab 16 to 90 for Fahrenheit or 9 to 32 for Celsius or Disabled Aux heat operation is locked out when outdoor temperature exceeds the Aux Heat Balance Point Dual fuel systems do not allow both t...

Страница 26: ...r auto or 0 for disabled battery saver 26 Selects the RF channel A fixed channel allows faster setup and reconnect when the gateway channel is fixed Auto channel allows more flexibility but may consum...

Страница 27: ...ool call on on also C icon will turn on N A Will test the cool call output Bypasses short cycle timers Useful for technician system testing Note that calling the cooling may activate other relays in t...

Страница 28: ...serviced or when there is an unexpected problem with it The display will flash the flame icon when the system is in Emergency Heat mode Cool Mode In Cool mode the thermostat uses the cooling system t...

Страница 29: ...ent the other setpoint will be automatically adjusted For example if the heat setpoint is at 68 degrees the cool setpoint is at 72 degrees and the Auto Dead Band is set to 4 degrees if you lower the c...

Страница 30: ...system program This is handled automatically by the Crestron CHV TSTATRF w 5 2 Scheduler module provided with the Crestron Database Refer to Programming with SIMPL Windows which starts on page 30 for...

Страница 31: ...setting Because of this there will be a noticeable delay between the time a button is pressed on a touchpanel and when the thermostat reacts to the command To account for this the CHV TSTATRF modules...

Страница 32: ...he setpoint is being adjusted if it is set to a half degree increment the integer portion of the number will be displayed and will alternate with _5 every quarter second for a period of four seconds a...

Страница 33: ...is being made C Displayed whenever a Cool Call is being made F Displayed whenever a Fan Call is being made A Displayed whenever an Aux Heat Call is being made 1 For heat pump and dual fuel systems whe...

Страница 34: ...ditional details download D3 Pro or SystemBuilder from the Crestron website and examine the extensive help files NOTE Heat pump and dual fuel heat pump systems require an outdoor temperature sensor e...

Страница 35: ...Library The system tree of the control system displays the device in the appropriate slot with a default MNET ID as shown in the following illustration C2Net Device Slot 9 Additional CHV TSTATRF devi...

Страница 36: ...ram a Crestron control system by assigning signals to symbols The symbol can be viewed by double clicking on the icon or dragging it into Detail View Each signal in the symbol is described in the SIMP...

Страница 37: ...ON TOOLBOX CONTROL SYSTEM SERIAL ETHERNET OR USB infiNET CRESNET CHV TSTATRF C2N MNETGW CHV TSTATRF connects to the C2N MNETGW Gateway which connects to the control system via Cresnet Establish commun...

Страница 38: ...re to upgrade the CHV TSTATRF firmware Since the CHV TSTATRF might be asleep there may be a delay of one minute or less before the update starts Program Checks Using Crestron Toolbox display the netwo...

Страница 39: ...k refer to Basic Thermostat Setup which starts on page 15 MNET ID of device or the gateway ID is not set to match the MNET ID of the SIMPL Windows program Use the Network Device Tree infiNET network i...

Страница 40: ...to Setup Mode Parameters Functions which starts on page 20 Wrong temperature scale Select F or C as necessary A Temperature Offset has been applied Reset Temperature Offset refer to Setup Mode Parame...

Страница 41: ...etical order by model number List of Related Reference Documents DOCUMENT TITLE 2 Series Control Systems Reference Guide C2N MNETGW infiNET Gateway Transceiver Further Inquiries If you cannot locate s...

Страница 42: ...heat that is blown through a duct system to heat the house The cycle begins again as the cooled liquid refrigerant is pumped back outside after releasing it s heat On the way it passes through an expa...

Страница 43: ...n of one system at a time only one balance point is available Blower Fan An air handling device for moving air in a distribution system Call A call is the action taken by the thermostat when it sends...

Страница 44: ...mperature error 0 5 to 3 0 to trigger the second stage 2 stage only such as the aux heat for a heat pump type system Run Fan in Heat Calls A device setting that activates the fan output during heat W...

Страница 45: ...ys batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regardin...

Страница 46: ...infiNET Thermostat Crestron CHV TSTATRF This page is intentionally left blank 42 infiNET Thermostat CHV TSTATRF Operations Installation Guide DOC 6490A...

Страница 47: ...Crestron CHV TSTATRF infiNET Thermostat Operations Installation Guide DOC 6490A infiNET Thermostat CHV TSTATRF 43 This page is intentionally left blank...

Страница 48: ...on Electronics Inc Operations Installation Guide DOC 6490A 15 Volvo Drive Rockleigh NJ 07647 2015101 Tel 888 CRESTRON 11 08 Fax 201 767 7576 Specifications subject to www crestron com change without n...

Отзывы: