background image

6 • CAEN-UMP1X2-DIN-PWS

Product Manual — Doc. 9310A

Specifications

Product specifications for the CAEN-UMP1X2-DIN-PWS.

Product Specifications

Power

Main Power

100-277VAC, 50/60 Hz

Available Power

30 W maximum from the

DIN-PWS30-277

Environmental

Temperature

41° to 113 °F (5° to 45 °C)

Humidity

10% to 90% RH (noncondensing)

Enclosure

Mounting Plate: Metal with attached DIN rail and tie-down anchors

Dimensions

Height

7.40 in. (188 mm)

Width

14 in. (356 mm)

Depth

2.91 in. (74 mm)

Содержание CAEN-UMP1X2-DIN-PWS

Страница 1: ...CAEN UMP1X2 DIN PWS CAEN Automation Enclosure Mounting Kit for 4 Series Automation Processor and Hub Product Manual Crestron Electronics Inc ...

Страница 2: ...l software_license_ agreement The product warranty can be found at www crestron com warranty The specific patents that cover Crestron products are listed at www crestron com legal patents Certain Crestron products contain open source software For specific information visit www crestron com opensource Crestron the Crestron logo 4 Series and Cresnet are either trademarks or registered trademarks of ...

Страница 3: ...he Box 8 Install the DIN HUB 9 Install the DIN AP4 10 Wire the DIN Rail Products 11 Mount the Plate to an Enclosure 13 Wire the CLX and DIN Rail Products 16 Resources 19 Crestron Support and Training 19 Programmer and Developer Resources 19 Product Certificates 19 Related Documentation 19 Product Manual Doc 9310A Contents iii ...

Страница 4: ...iv Contents Product Manual Doc 9310A ...

Страница 5: ...to a CAEN CAEN MLO or CAENIB automation enclosure sold separately The CAEN UMP1X2 mounting plate is equipped with a DIN rail and a DIN PWS30 277 30 W Cresnet power supply The CAEN UMP1X2 DIN PWS also includes DIN rail end clamps screws and cables for connecting the DIN products For additional details refer to the DIN PWS30 277 and CAEN UMP1X2 product pages Physical Description The diagram identifi...

Страница 6: ...fications Power Main Power 100 277VAC 50 60 Hz Available Power 30 W maximum from the DIN PWS30 277 Environmental Temperature 41 to 113 F 5 to 45 C Humidity 10 to 90 RH noncondensing Enclosure Mounting Plate Metal with attached DIN rail and tie down anchors Dimensions Height 7 40 in 188 mm Width 14 in 356 mm Depth 2 91 in 74 mm ...

Страница 7: ...Product Manual Doc 9310A CAEN UMP1X2 DIN PWS 7 Dimension Drawings ...

Страница 8: ...d clamp and retighten the screw Refer to step 2 of Install the DIN AP4 on page 10 In the Box Qty Description 1 CAEN UMP1X2 DIN PWS CAEN Automation Enclosure Mounting Kit for 4 Series Automation Processor and Hub Additional Items 1 Cable 4 Wires 6 in 153 mm Round 4519362 1 Cable 5 Wires PCB Connectors 18 in 457 mm Flat 4531268 1 Cable 2 Wires 2 Pin Terminal Block Connector 8 in 203 mm Round 4534582...

Страница 9: ... the DIN HUB l Three jumper wires included with the CAEN UMP1X2 DIN PWS To install the DIN HUB 1 Connect the three 3 pin terminal blocks 2 Insert the jumper wires into the 3 pin terminal blocks Ensure the wires are fully inserted in the terminals 3 Use a small flat head screwdriver to secure the wires by tightening the screws on the terminal block Tighten to 2 in lbs 0 25 nm 4 Use a small flat hea...

Страница 10: ...tion guide for details 6 Connect the remaining terminal blocks or save them for future use Install the DIN AP4 The DIN AP4 is not included with the CAEN UMP1X2 DIN PWS Included equipment with the DIN AP4 l One 2 Pin terminal block l Two 4 Pin terminal blocks l Two 5 Pin terminal blocks l Two 8 Pin terminal blocks l One 9 Pin terminal block ...

Страница 11: ...lamp next to the DIN AP4 Tighten to 9 in lbs 1 02 nm 3 Connect six of the terminal blocks included with the DIN AP4 or save them for future use Refer to the diagram for placement Wire the DIN Rail Products To connect the DIN products use the following equipment included with the CAEN UMP1X2 DIN PWS l 2 wire cable with flying leads on one end and a 2 pin terminal block on the other l 4 wire cable w...

Страница 12: ...t flying leads Ensure the wires to the DIN PWS30 277 terminals are fully inserted l Connect the black wire to the negative terminal using a small flat head screwdriver Tighten to 3 in lbs 0 34 nm l Connect the red wire to the positive terminal using a small flat head screwdriver Tighten to 3 in lbs 0 34 nm 2 Connect the NET output on the DIN AP4 to the NET HOST input on the DIN HUB using the 4 wir...

Страница 13: ...th the retained ground screw from step 5 Tighten to 9 in lbs 1 02 nm c Layer a screw flat washer and lock washer all included with the CAEN UMP1X2 DIN PWS over the UMP1X2 plate grounding hole as shown below d Use a Phillips screwdriver to secure the screw to the UMP1X2 plate Tighten to 9 in lbs 1 02 nm Mount the Plate to an Enclosure To mount the CAEN UMP1X2 DIN PWS to a CAEN CAEN MLO or CAENIB au...

Страница 14: ...the enclosure Ensure the flanges of the plates do not overlap other plates or lighting modules that are mounted in the enclosure NOTE In a single wide enclosure install the CAEN UMP1X2 DIN PWS in the bottom module position In a double wide enclosure install the CAEN UMP1X2 DIN PWS in the bottom two module positions ...

Страница 15: ...Product Manual Doc 9310A CAEN UMP1X2 DIN PWS 15 Refer to the following diagrams for example CAEN UMP1X2 DIN PWS placement in an enclosure CAEN UMP1X2 DIN PWS in a 2x1 Enclosure ...

Страница 16: ...rcuit breaker or fuse and test that power is off before wiring NOTES l Install and use the assembly in accordance with appropriate electrical codes and regulations l A licensed electrician must install the assembly l When installing in an enclosure group high voltage devices separately from low voltage devices l Use copper wire only For high voltage connections use wires rated for at least 75 C l ...

Страница 17: ...WS 17 1 Connect the following cables included with the CAEN UMP1X2 DIN PWS l The 6 in 153 mm cable connects a CAEN BLOCK Cresnet port to the DIN AP4 Cresnet port l The 18 in 457 mm flat cable connects the CAEN BLOCK to the CLX module connector ...

Страница 18: ...nsure the power supply is properly grounded NOTE The DIN HUB and CAEN BLOCK only receive power when powered via the DIN PWS30 277 If the DIN AP4 is powered via PoE not recommended it will not pass power to the DIN HUB or CAEN BLOCK 3 Wire the CAEN UMP1X2 DIN PWS Refer to the DIN AP4 and DIN HUB manuals ...

Страница 19: ...rt l Crestron Resource Library l Crestron Online Help OLH l Crestron Training Institute CTI Portal Programmer and Developer Resources l help crestron com Provides help files for Crestron programming tools such as SIMPL SIMPL and Crestron Toolbox software l developer crestron com Provides developer documentation for Crestron APIs SDKs and other development tools Product Certificates To search for p...

Страница 20: ...Crestron Electronics Inc 15 Volvo Drive Rockleigh NJ 07647 Tel 888 CRESTRON Fax 201 767 7656 www crestron com Product Manual Doc 9310A 2054547 06 15 22 Specifications subject to change without notice ...

Отзывы: