Crestron C2N-UNI8IO Скачать руководство пользователя страница 1

C2N-UNI8IO

Universal Keypad Interface
Installation & Operation Guide

Additional Resources

Visit the product page on the Crestron website (www.crestron.com) 
for additional information and the latest firmware updates. Use a QR 
reader application on your mobile device to scan the QR image.

Hardware Hookup

The following diagram shows a C2N-UNI8IO in a lighting and AV system application.

Connectors, Controls, and Indicators

The following diagram shows a C2N-UNI8IO in a lighting and AV system application.

Wiring Diagrams

CAUTION

:  Shorting non-current limited supplies may cause damage to the outputs 

on the unit.

Internal 5V LED Driver (Internal 5 mA 5 V Current Limit)

NOTE

:  Dip switches must be in the OFF position.

NOTE

:  Internal 5 mA 5 V current limit can be enabled or disabled on an individual 

basis.

Description

The Crestron

®

 C2N-UNI8IO is a compact interface designed to allow virtually any keypad 

to be connected directly to a Cresnet

®

 control network. The Cresnet network is the 

communications backbone for Crestron sensors, dimmers, keypads, touch panels, 
shade controllers, thermostats, and many other devices. This flexible 4-wire bus provides 
data communications and 24 Vdc power for all of the devices on the Cresnet network. 
The C2N-UNI8IO installs easily at the keypad location, sitting conveniently inside the 
electrical box behind the keypad. Wiring connections to the network are made using a 
detachable terminal block connector. Wiring connections to the keypad can be made 
using the provided connectors with flying leads, or the keypad manufacturer can choose 
to mate directly to the exposed connectors.
The C2N-UNI8IO is compatible with most keypads that provide contact closures as user 
inputs and use LEDs for feedback. Up to 1 A @ 24 Vdc power and 40 mA @ 5 Vdc is 
available to support a variety of keypads. The C2N-UNI8IO includes eight sensing inputs, 
each capable of sensing a contact closure. The C2N-UNI8IO also includes eight 
open-drain outputs capable of sinking up to 100 mA each (500 mA maximum total 
current). Also provided are eight current-limiting resistors that can be switched in series 
with each channel to limit the output current to 5 mA @ 5 Vdc.
Specifications for the C2N-UNI8IO are listed below.

Installation

WARNING

:  To avoid fire, shock, or death, turn off the power at the circuit breaker or 

fuse and test that the power is off before wiring! 

NOTE

:  Observe the following points:

  •  Install and use this prodcut in accordance with appropriate electrical codes and 

regulations.

  •  A licensed electrician must install this product.

NOTE

:  Before using the C2N-UNI8IO, ensure the device is using the latest firmware. 

Check for the latest firmware for the C2N-UNI8IO at www.crestron.com/firmware. Load 
the firmware onto the device using Crestron Toolbox™ software.

The C2N-UNI8IO can be installed inside a standard electrical box. Refer to the following 
illustration.

Installing the IDC Connector and the Cresnet Connector

OUTPUT

INPUT

G G  1  2  3  4  5  6  7  8

5V  1  2  3  4  5  6  7  8  2

4V

Third-party keypad

C2N-UNI8IO

Control

processor

A/V

system

Lighting

system

Cresnet

Multiwire cable

OUTPUT

INPUT

Removing the IDC Connector

Use a flat-blade screwdriver to loosen the IDC connector from the header. Place the 
flat-blade screwdriver between the header and midsection of the connector. Turn the 
screwdriver to pry the IDC connector up.

Using a Third-Party Keypad

OUTPUT

INPUT

G G  1  2  3  4  5  6  7  8

5V  1  2  3  4  5  6  7  8  2

4V

GND

GND

LED

LED

LED

LED

LED

LED

LED

LED

1

2

3

4

5

2.05 in

(52 mm)

0.51 in

(13 mm)

2.13 in

(54 mm)

0.69 in

(18 mm)

2.07 in

(53 mm)

SPECIFICATION 

DETAILS 

Power Requirements 

 

 

Cresnet Power Usage 

0.5 W (0.02 A @ 24 Vdc) 
Does not account for LED, bulbs, or other device's 

power consumption. 

Ratings 

 

 

Digital Inputs 

(8) Inputs rated for 0-24 Vdc, includes 10 KΩ pull-up 

to 5 Vdc 
Logic low threshold: ≤1 V  

Logic high threshold: ≥3.7 V 

 

Digital Outputs 

(8) Open drain outputs rated for 100 mA @ 24 Vdc, 
500 mA max (combined for all 8 outputs), when not 

in Current Limit mode 
Maximum Power Load: 1 A @ 24 Vdc and  
40 mA @ 5 Vdc.

 

Actual load capability dependent 

upon the amount of available Cresnet power in the 

system.

 

Environmental 

 

 

Temperature 

32°F to 104°F (0°C to 40°C) 

 

Humidity 

10% to 95% RH (noncondensing) 

Dimensions 

 

 

Height 

2.06 in (53 mm) 

 

Width 

2.05 in (52 mm) 

 

Depth 

0.68 in (18 mm) 

Weight 

1 oz (24 g) 

 

CONNECTORS, 

CONTROLS, AND 

INDICATORS 

DESCRIPTION 

SETUP 

(1) Red LED and (1) miniature push button, used 
for touch-settable ID (TSID) 

OUTPUT CURRENT 

LIMIT 

(1) 8-position DIP switch, engages 1 K ohm 
current limiting resistor per output, limits each 

output to 5mA @ 5VDC for use with LEDs 

NOTE

: When in “current limit” mode, be sure to 

not exceed the above rating. 

NET 

(1) 4-pin 3.5mm detachable terminal block; 
Cresnet slave port, connects to Cresnet control 

network 

OUTPUT 

(1) 10-pin 0.1” IDC connector, includes (10) single 
conductor 22 AWG 3” flying leads Outputs 
comprised of (1) 24VDC, (1) 5VDC, and (8) digital 

outputs (referenced to GND) 
Note: 24V connector is a Cresnet power pass-

through. 

INPUT 

(1) 10-pin 0.1 in (3 mm) IDC connector comprised 
of (10) single-conductor 22 AWG 3 in (76 mm) 

flying leads 
Inputs comprised of (2) GND references and (8) 

digital inputs (referenced to GND) 

 