INSTALLATION INSTRUCTIONS
IFW 66 SERIES INFRA RED WARMER
5925 Heisley Road • Mentor, OH 44060-1833
Decorator Hood
IFW 66 Series
FL-2194
Rev. 5 (07/10)
Page 1 of 2
Call Toll-free: 877-CRES COR (273-7267) • Fax: 800-822-0393 • www.crescor.com
ELECTRICAL SPECS:
VOLTS WATTS
AMPS
HERTZ PHASE
NEMA
120
250
2.0
60
1
5-15
240
275
1.1
60
1
6-15
Warmer should be installed by an experienced
electrician.
U.L. REQUIREMENTS:
A. Wires of warmers to be connected to 75°C wire.
B. Wires are to be installed in conduit.
C. Warmers are not to be installed any closer than 1” from
a wall.
D. Warmers must be
at least
16” above a combustible
surface.
HOW TO INSTALL:
Numbers in parentheses correspond to numbers in callouts.
Remove the two screws from the canopy and pull off
1.
the canopy.
Run the cord (1) up through the canopy, through the
2.
strain relief and the threaded nipple. Tighten the strain
relief. Cut the cord to the desired length.
Mount the strap to the electrical outlet box with two
3.
screws provided.
Wire the warmer leads to the outlet box leads.
4.
Attach the ground wire to the ground hold in the strap
5.
with the green ground screw.
Re-attach the canopy with the two screws.
6.
Screw the bulb (4) into socket.
7.