BACnet Implementation
The eDIDIO S10 has an optional BACNET implementation that can be provided at time of order.
•
Description - Lighting Controller
•
Vendor Name - Ctrl Freak
•
Vendor ID - 812
•
Model - edidio-s10
The device implements a BACNET lighting object and simplifies the DALI/BACNET relationship by offering various
commands.
Lighting Objects -
There are 32 instances available, broken down into DALI Groups 0-15 on DALI Line 1 and DALI Groups
0-15 on DALI Line 2.
Default properties use 2.8s Fade time, with a step increment of 44/256.
The following commands are available.
•
BACNET_LIGHTS_FADE
o
Optional use fade time
•
BACNET_LIGHTS_STEP_UP
o
Uses DALI Step Up Function
•
BACNET_LIGHTS_STEP_DOWN
o
Uses DALI Step Down Function
•
BACNET_LIGHTS_STEP_ON
o
100% Level using inbuilt fade time
•
BACNET_LIGHTS_STEP_OFF
o
0% Level using inbuilt fade time
To reduce DALI traffic, RAMP is not suggested and is not active by default. Light commands are recommended to be
sent as BACNET_LIGHTS_FADE with use_fade_time TRUE for optimal results. Present Value is tracked and can be read
from system
Binary Value Objects
Binary Value objects allow for quick and easy commands to be sent to the controller. The polling command allows
polling to begin, which will check on the status of all devices at a 1 second interval (64 seconds per line). The General
Fault values will show a 1 if any of the devices on that line recorded with a DALI ‘Status’ or ‘Lamp’ failure. Once the
failure is rectified, either allow ~2 minutes for the fault to clear or write the value as 0.
Instance
Property
Read/Write
Present Value = 0
Present Value = 1
0
DALI Line 1 Master On/Off
R/W
DALI Line 1 0%
DALI Line 1 100%
1
DALI Line 2 Master On/Off
R/W
DALI Line 2 0%
DALI Line 2 100%
2
DALI Line 1 Sensors
R/W
Mute All Line 1
Unmute All Line 1
3
DALI Line 2 Sensors
R/W
Mute All Line 2
Unmute All Line 2
4
Poll Lines
R/W
Polling Disabled
Polling Active
5
General Fault Line 1
R/W
No Fault Line 1
Fault Detected Line 1
6
General Fault Line 2
R/W
No Fault Line 2
Fault Detected Line 2