MODEL
HP
VOLT PH
RPM
NEMA
FULL
LOCKED CORD
CORD
CORD
WINDING
NO.
(Nom) CODE
LOAD
ROTOR
SIZE
TYPE
OD
RESISTANCE
AMPS
AMPS
MAIN
6SE10036EHA
10
230
3
1150
H
31.0
161.0
8/4
SOW-A
0.985
0.39
6SE10046EHA
10
460
3
1150
H
15.5
80.5
8/4
SOW-A
0.985
1.59
6SE15036EHA
15
230
3
1150
G
39.0
218.0
8/4
SOW-A
0.985
0.24
6SE15046EHA
15
460
3
1150
G
19.5
109.0
8/4
SOW-A
0.985
0.99
6SE20036EHA
20
230
3
1150
G
54.0
284.0
6/4
SOW-A
1.125
0.18
6SE20046EHA
20
460
3
1150
G
27.0
142.0
6/4
SOW-A
1.125
0.73
6SE25036EHA
25
230
3
1150
G
68.0
346.0
4/4
SOW-A
1.350
0.13
6SE25046EHA
25
460
3
1150
G
34.0
173.0
4/4
SOW-A
1.350
0.53
6SE30046EHA
30
460
3
1150
G
40.0
210.0
2/4
SOW-A
1.500
0.36
6SE30034EHA
30
230
3
1750
G
78.0
414.0
2/4
SOW-A
1.500
0.11
6SE30044EHA
30
460
3
1750
G
39.0
207.0
2/4
SOW-A
1.500
0.45
6SE40034EHA
40
230
3
1750
F
104.0
550.0
2/4
SOW-A
1.500
0.10
6SE40044EHA
40
460
3
1750
F
52.0
275.0
2/4
SOW-A
1.500
0.33
6SE50044EHA
50
460
3
1750
F
63.0
336.0
4/4
SOW-A
1.350
0.16
6SE60044EHA
60
460
3
1750
F
77.3
410.0
2/4
SOW-A
1.500
0.15
6SE75044EHA
75
460
3
1750
F
92.0
504.0
2/4
SOW-A
1.500
0.11
6SE100044EHA
100
460
3
1750
G
120.0
703.0
1/4
SOW-A
1.680
0.08
Winding Resistance
±
5%. Pump rated for operation at
±
10% voltage at motor.
Moisture/Temperature sensor cable for all models is 18/5 SO, 0.476 O.D.
SECTION: D START-UP OPERATION
D-1) Check Voltage and Phase:
Before operating pump, compare the voltage and phase information
stamped on the pump identification plate to the available power.
D-2) Check Pump Rotation:
Before putting pump into service for the first time, the motor rotation
must be checked. Improper motor rotation can result in poor pump
performance and can damage the motor and/or pump. To check the
rotation, suspend the pump freely, momentarily apply power and
observe the "kickback". "Kickback" should always be in a
counter-clockwise direction as viewed from the top of the pump motor
housing.
D-2.1) Incorrect Rotation for Three-Phase Pumps:
In the event that the rotation is incorrect for a three-phase installation,
interchange any two power cable leads at the control box.
DO NOT
change leads in the cable housing in the motor. Recheck the
"kickback" rotation again by momentarily applying power.
D-2.2) Incorrect Rotation for Single-Phase Pumps:
In the unlikely event that the rotation is incorrect for a single phase
pump, contact a Barnes Pumps Service Center.
D-3) Start-Up Report:
Included at the end of this manual are two start-up report sheets,
these sheets are to be completed as applicable. Return one copy to
Barnes Pumps, Inc. and store the second in the control panel or with
the pump manual if no control panel is used. It is important to record
this data at initial start-up since it will be useful to refer to should
servicing the pump be required in the future.
D-3.1) Identification Plate:
Record the numbers from the pump identification plate on both
START-UP REPORTS provided at the end of the manual for future
reference.
D-3.2) Insulation Test:
Before the pump is put into service, an insulation (megger) test
should be performed on the motor. The resistance values (ohms) as
well as the voltage (volts) and current (amps) should be recorded on
the start-up report.
D-3.3) Pump-Down Test:
After the pump has been properly wired and lowered into the basin,
sump or lift station, it is advisable to check the system by filling with
liquid and allowing the pump to operate through its pumping cycle.
The time needed to empty the system, or pump-down time along with
the volume of water, should be recorded on the start-up report.