- 53 -
GAS CONVERSION
- Combustion product evacuation outlet back pres-
sure: 0 mmCE.
-
P
o
= Gas pressure at the gas valve regulator out-
let.
-
PL
= Servo-system air pressure (burner/gas
unit).
- The Po and PL values may be more or less high
according to whether back pressure is greater or
smaller.
3.2 - Setting table
Modèles
THI 10-50
Burner type
X00.22519
Heat output
30/50 °C
60/80 °C
kW
kW
10,7/52,6
9,7/48,7
Heat input
kW
10,0/50,0
Æ
Gas reducer Nat
Gas
H
Propane
mm
mm
-
6,40
Æ
Air reducer Nat
Gas
H
Propane
mm
mm
-
31
Gas flow (15 °C 1013 mbar)
Nat
Gas
H
Propane
m
3
/h
kg/h
1,06/5,29
0,78/3,88
Gas pressure P
o
(Gas unit to burner)
mbar
0,25/2,4
Air pressure servo-system (PL)
Pa
40/630
CO
2
Emission Nat
Gas
H
Propane
%
%
8,0-8,5/9,0-9,5
10,0-10,5/10,5-11,0
CO Emission Nat
Gas
H
Propane
ppm
ppm
0/20
0/40