The parameters
p1
to
p8
are changed in the same way
as
p1
. After step 2, use the
[+]
key to move to the
required parameter.
5.7.3.
Modification of the installer-level
parameters
Parameters
p17
to
df
must only be modified by a qualified
professional. To prevent unwanted settings, some parameter settings
can only be changed after the special access code
0012
is
entered.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
1. Press the two keys
f
simultaneously and then key
[+]
until the
symbol
?
flashes on the menu bar.
2. Select the fitter menu using the
®
key.
c0de
appears on the
display.
3. Use keys
[-]
or
[+]
to input the installer code
0012
.
4. Confirm using key
S
.
p[1
is displayed with
1
flashing.
5. Press the
S
key a second time. The value
80
°C appears and
flashes (for example).
6. Change the value by pressing the
[-]
or
[+]
key. In this example
using key
[-]
to
60
°C.
7. Confirm the value with the
S
key:
p[1
is displayed with
1
flashing.
8. If necessary, set other parameters by selecting them using the
[-]
or
[+]
keys.
9. Press the
>
key 2 times to return to the current operating
mode.
The boiler also returns to operating status if no keys are
pressed for 3 minutes.
5.7.4.
Setting the maximum heat input for central
heating operation
Quinta Pro 30
M
Maximum heat input
F
Factory setting
Q
Power input (kW)
R
Fan rotation speed (rpm)
T000819-E
3x
2x
R000035-A
1500
2500
3500
4500
5500
6500
7500
0
20
R
Q
40
30
F
M
4100
5. Commissioning
Quinta Pro 30 - 45 - 65 - 90 - 115
58
250413 - 123157-03
Содержание Quinta Pro 115
Страница 7: ...250413 123157 03 5 ...
Страница 88: ...10 Checklists Quinta Pro 30 45 65 90 115 86 250413 123157 03 ...
Страница 89: ...Quinta Pro 30 45 65 90 115 10 Checklists 250413 123157 03 87 ...
Страница 90: ...10 Checklists Quinta Pro 30 45 65 90 115 88 250413 123157 03 ...
Страница 91: ......