4
Jumper 2: The settings for central heating and sanitary hot water
are reversed.
4.9.7.
Connection possibilities for the PCB (SCU-
X03)
The control PCB SCU-X03 can control a modulating central heating
pump. Depending on the make and type of pump, the pump can be
controlled by a 0-10 V, 4-20 mA or PWM signal. The speed of the
pump is modulated, based on the signal received from the boiler.
For correct connection of the pump, see the documentation
supplied with the pump.
n
Connect on/off contact
Connect the on/off contact of the central heating pump to the
connector
X1
.
CAUTION
Do not use the on/off contact to interrupt the power supply
to the pump.
n
Connect central heating pump
The control system of the central heating pump is connected to
connector
X2
.
Select the type of signal that will be received from the boiler using the
rotary knob
SW1
on the control PCB. See table below:
No. Description
0
Pump modulation signal
1
Required heat output of boiler
2
Current heat output of boiler
3
-
4
-
5
-
6
-
7
-
8
-
9
-
T002038-B
X4
X3
SCU-X03
X2
X1
Ctrl
0 +
0
+
4. Installation
Quinta Pro 30 - 45 - 65 - 90 - 115
40
250413 - 123157-03