Type
Execution
Description
C33
Closed
4
Exhaust of combustion gases above the roof.
4
The opening for the air-supply inlet is located in the same pressure zone as the vent (For
example, a concentric passage to the roof).
C43
(2)
Closed/Cascade
4
Common channelling for the air-supply and exhaust of combustion gases (CLV):
-
Concentric.
-
Eccentric; Air supply from the shaft.
4
This also relates to the overpressure cascades.
C53
Closed
4
Closed equipment.
4
Separate channelling for the air-supply.
4
Separate channelling for the combustion gases.
4
Terminating on different pressure surfaces.
C63
Closed
4
The manufacturer delivers this type of equipment without a supply or exhaust system.
C83
(3)
Closed
4
The equipment can be connected on a so-called semi-CLV system (with common combustion
gas exhaust).
C93
(4)
Closed
4
Channel for the air-supply and exhaust fumes in a duct or surrounded by a sleeve:
-
Concentric.
-
Eccentric; Air supply from the shaft.
-
Exhaust of combustion gases above the roof.
-
The opening for the air-supply inlet is located in the same pressure zone as the vent.
(1) Including the pressure classification P1
(2) EN483: 0,5 mbar suction by pressure reduction
(3) An under pressure of 4 mbar is possible
(4) See table for minimum sizes of duct or sleeving
Type Execution Diameter
Minimum size of the duct or jacket
Without air-supply
With air-supply
∅
Channel
⃞
Channel
∅
Channel
⃞
Channel
C93 Rigid
60 mm
110 mm
110 x 110 mm
120 mm
110 x 110 mm
80 mm
130 mm
130 x 130 mm
140 mm
130 x 130 mm
100 mm
160 mm
160 x 160 mm
170 mm
160 x 160 mm
Flexible
60 mm
110 mm
110 x 110 mm
120 mm
110 x 110 mm
80 mm
130 mm
130 x 130 mm
145 mm
130 x 130 mm
100 mm
160 mm
160 x 160 mm
170 mm
160 x 160 mm
Concentric
60/100 mm
120 mm
120 x 120 mm
120 mm
120 x 120 mm
80/125 mm
145 mm
145 x 145 mm
145 mm
145 x 145 mm
100/150 mm
170 mm
170 x 170 mm
170 mm
170 x 170 mm
4.7.2.
Outlets
For exhausting combustion gases of types C1, C3 and C5, it is
appropriate to use a
M&G Skyline / Mugro 3000
or a
Coxstand E
HR
. When exhausting combustion gases of type C6, the material of
the exhaust must conform with Gastec QA and/or be provided with
CE marking.
The exhaust vent for combustion gases must conform to EN
1856-1. The flue gas pipes must be calculated conforming to EN
13384 (parts 1 & 2).
For open exhaust of combustion gases above the roof, the
vent must always be provided with a suitable stainless steel
wire grill.
Quinta Pro 30 - 45 - 65 - 90 - 115
4. Installation
250413 - 123157-03
23
Содержание Quinta Pro 115
Страница 7: ...250413 123157 03 5 ...
Страница 88: ...10 Checklists Quinta Pro 30 45 65 90 115 86 250413 123157 03 ...
Страница 89: ...Quinta Pro 30 45 65 90 115 10 Checklists 250413 123157 03 87 ...
Страница 90: ...10 Checklists Quinta Pro 30 45 65 90 115 88 250413 123157 03 ...
Страница 91: ......