APP Interface
56 / 79
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
Unit
QSetPercentLoca
l
Local Reactive power
derating percent
{-66%,66%}
0.0%
0.0%
0.0%
%
PFSetValue
PF setting value
{-1,-
0.8},{0.8,1}
-0.950
1
NA
ReactivePowerOv
er
Reactive power over
matching
{ Enable }
Enable
Enable
Enable
Table 6-5 ReactivePowerDerating Para. (IEEE1547 2018, Rule21 and ISO-NE)
LcdLess Basic Parameters
The LcdLess Basic Parameters interface is used to set the parameters as below.
Figure 6-19 LcdLess Basic Parameters interface
The last three registers are configured as standard, i.e. the inverter supports IV curve
function, Automatic MdbsAdr assignment function and the Fault recording function.
However, almost all these parameters are read-only, that means you cannot change
them randomly. More information, please contact the after-sale service personnel.
Firmware Upgrade
As to the detailed procedures for firmware upgrade, Refer to specific instructions or
consult our after-sale support personnel.
6.4.3
History
Touch the History icon, it will go to the History interface.
There are 2 submenus in the History menu: “Warning” and “Running Status”.