APP Interface
53 / 79
UFDerEn
under frequency
derating enable
{Disable, Enable}
Disable
Disable
Disable
CtrModeActivePw
Active power control
mode
{ Disable
dispatch mode,
Remote dispatch
mode, Local
control}
Disable
dispatch
mode
Disable
dispatch
mode
Disable
dispatch
mode
PSetPercentLocal
Local Active power
derating percent
{0%,110%}
100%
100%
100%
%
ActivePowerOver
Active power over
matching
{Disable, Enable}
Enable
Enable
Enable
Table 6-4 ActivePower Derating para. (IEEE1547 2018, Rule21 and ISO-NE)
ReactivePowerDerating
The ReactivePowerDerating interface is used to set the Grid reactive power derating
parameters, including PF parameters and Qu parameters, etc.
Figure 6-16 The ReactivePowerDerating interface
Note: The PF and Q value can be adjusted by remote software if the “Remote” is
selected.
PF Set: Set the PF value. Note: Change the reactive power by adjusting
the power factor.
PF(P) Curve
:
PF curve mode. Note: The power factor changes according
to the power change, as shown in Figure 6-17.
IMPORTANT!
The PF (P) Curve function is only available for IEEE1547 Grid Codes.