APP Interface
49 / 79
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
Unit
GFCIDynProEn
Enable Dynamical
ground fault circuit
interrupter
{Disable, Enable}
Disable
Disable
Disable
DCIProtection1
Max. DCI value 1
{0.1%,5.00%}
0.50%
0.50%
0.50%
%
DCIProtectionT1
Trip time 1 of DCI
value
{0.00,120.00}
10.00
10.00
60.00
Secs
DCIProtection1En
Enable Maximum
DCI value 1
{Disable, Enable}
Enable
Enable
Enable
DCIProtection2
Max. DCI value 2
{5,5000}
950
950
950
mA
DCIProtectionT2
Trip time 2 of DCI
value
{0.00,120.00}
1.00
1.00
1.00
Secs
DCIProtection2En
Enable Max. DCI
value 2
{Disable, Enable}
Disable
Disable
Disable
PVStartupVolt
PV start-up voltage
(500, 700)
550
550
550
V
MPPTScanPeriod
MPPT Scan Cycle
{300,5400}
3600
3600
3600
Secs
MPPTScanEn
Enable MPPT Scan {Disable, Enable}
Disable
Disable
Disable
ISOProtection
Minimum insulation
resistance
{1, 5000}
100
100
100
k
Ω
ISOProtectionEn
Insulation detection {Disable, Enable}
Enable
Enable
Enable
StartUpMinTemp
Min Startup
Temperature
{-35
℃
, -20
℃
}
-30
-30
-30
℃
DuplicationControl
Duplication Control
{0%,100%}
0%
0%
0%
%
PID Check Settings
PID Check Setting {Disable, Enable}
Disable
Disable
Disable
Island Protect
anti-Island protection {Disable, Enable}
Enable
Enable
Enable
FANDetectEn
fans detection
{Disable, Enable}
Enable
Enable
Enable
ACSPDDetectEnSet
AC surge protection
device test
{Disable, Enable}
Disable
Disable
Disable
OperationOverVol
Operation over
voltage protect value
{100%,135%}
120%
120%
120%
%
OperationOverVolD
ectEn
Over voltage
detection
{Disable, Enable}
Disable
Disable
Disable
VirtualDamping
Resonance damping
coefficient
{0.000, 5.000}
0.000
0.000
0.000
Ω
MPPTRangEnable
Enable MPPT
{Disable, Enable}
Disable
Disable
Disable
RapidShutdownEna
bBit
Enable Rapid
Shutdown
{Disable, Enable}
Disable
Disable
Disable
FreqLv2PrtEn (CEI)
Only for Italian Grid
Code
{Disable, Enable}
Disable
Disable
Disable
PVxxFuseCheckEn
(xx=1..24)
Enable the fuse
check function
{Disable, Enable }
OptiVoltMinMpptxx
(xx=1..12)
Minimal voltage of
Mppt optimizer
{500, 1450}
500
500
500
V
OptiVoltMaxMpptxx
(xx=1..12)
Maximal voltage of
Mppt optimizer
{500, 1450}
1450
1450
1450
V
Table 6-3 Other Parameters (IEEE1547 2018, Rule21 and ISO-NE)
Command
In the Command interface, you can access the following infomation:
Содержание SCH275KTL-DO/US-800
Страница 40: ...APP Interface 40 79 Figure 6 7 Protection Parameters ...
Страница 47: ...APP Interface 47 79 Others In the others interface you can find following common parameters shown as below ...
Страница 57: ...APP Interface 57 79 Figure 6 20 History interface 6 4 4 Turn ON OFF Figure 6 21 Turn ON OFF interface ...