CPS Pro-Set LDA1000H Скачать руководство пользователя страница 1

Pro-Set

    

LDA1000H

Refrigerant Leak Detector

OPERATION MANUAL

US Patent Number 8,555,701

Содержание Pro-Set LDA1000H

Страница 1: ...Pro Set LDA1000H Refrigerant Leak Detector OPERATION MANUAL US Patent Number 8 555 701 ...

Страница 2: ... 12 Table of Contents 2 Introduction Press to turn on press to change sensitivity press and hold for 3 seconds to turn unit off White LED S indicate sensitivity setting for HFO 1234yf Blue LED S indicate sensitivity setting for R 134a Flexible metal probe 15 380mm long 25 6 4mm diameter High output alarm speaker Bar graph display Green LED indicates low battery Sensor inside protective metal housi...

Страница 3: ...performance as indicated under J2791 and J2913 which can be removed and cleaned if the opening gets clogged with dirt In areas where humidity is high the patented CPS Water Vapor Filter cap is recommended to eliminate false alarms One LS2VF water vapor filter cap is included with the LDA1000H FEATURES Microprocessor controlled sensor electronics utilizing a multi channel signal detection method im...

Страница 4: ...inated atmosphere The LDA1000H gives an indication within 5 seconds when the probe is held stationary at 5mm 0 2 from a calibrated leak source of R 134a set for 3 g yr per EN14624 2012 Audible Alarms High pitched wide tone range audible alarm alarm in settings L M and S Low pitched audible alarm in SC settings Visual Alarms An 8 segment bar graph LED display shows the relative leak size Operating ...

Страница 5: ...to advance the sensitivity to the 7 g yr 0 25 oz yr If no indication is obtained in this range then press START again and go the highest sensitivity setting of 4 g yr 0 15 oz yr Pressing the START button once again puts the LDA1000H in a unique setting especially designed to be used in heavily con taminated atmospheres This setting is identified by a lower tone alarm which increases in volume and ...

Страница 6: ... controls service ports with caps in place brazed or welded areas and areas around attachment points and hold down on lines and components If looking for an apparently larger leak check first at 7g yr or 14 g yr settings 4 Turn on the LDA1000H and allow it to warm up outside the area to be searched Based on an estimate of the system s leak rate set the LDA1000H to the appropriate refrigerant and s...

Страница 7: ...ize Use the 7g yr 0 25 oz yr setting after finding an apparent leak with the 4g yr 0 15 oz yr setting may also be helpful 8 When testing for a leak at the compressor move the probe along the compressor body joints along the pressure relief valve any switches and the all around the compressor shaft seal area Shaft seals normally leak during compressor operation so it may be very difficult to ascert...

Страница 8: ...ce lotion hand cleaner Yes Yes Motorcraft DOT3 brake fluid No Ford spray carburetor tune up cleaner Yes Yes Ford silicone lubricant No Windshield washer solvent methanol base Yes Yes Permatex natural blue cleaner and degreaser Yes Yes Gunk liquid wrench Yes Yes Dextron automatic transmission fluid heated to 160 F No Mineral engine oil heated to 160 F No CAUTION This leak detector is sensitive to s...

Страница 9: ... lotion hand cleaner Yes Yes Motorcraft DOT3 brake fluid No Ford spray carburetor tune up cleaner Yes Yes Ford silicone lubricant No Windshield washer solvent methanol base Yes Yes Permatex natural blue cleaner and degreaser Yes Yes Gunk liquid wrench Yes Yes Dextron automatic transmission fluid heated to 160 F No Mineral engine oil heated to 160 F No 9 CAUTION This leak detector is sensitive to s...

Страница 10: ... to loosen the dirt and blow with compressed air Clean the O ring and replace Do not cover the O ring with Vaseline or any other lubricant Install the replacement sensor Orient the tab on the edge of the sensor so it coincides with the groove on the side of the housing and gently push the sensor in Do not use silicone based hand cleaners or lotions prior to installing a new sensor as this will irr...

Страница 11: ...OPERATION Sensor Replacement Diagram 11 Replacement Parts EMOS2 Replacement EMOS sensor LS2XVF Water vapor filter ...

Страница 12: ...r contact information WARRANTY 12 CPS Products Inc U S A Headquarters 1010 East 31st Street Hialeah Florida 33013 USA Tel 305 687 4121 1 800 277 3808 Fax 305 687 3743 E mail info cpsproducts com Website www cpsproducts com CPS CANADA LTD 6934 Kinsmen Court Unit C Niagara Falls Ontario L2E 3S5 Tel 905 358 3124 Fax 905 358 7187 1 866 629 3895 E mail cpscanada bellnet ca CPS PRODUCTS N V Krijgsbaan 2...

Страница 13: ...NOTES ...

Страница 14: ...www cpsproducts com 73 358 Rev C ...