Document Part # 026-4824 Rev 0 5/8/2007

Page 1 of 2

©2007 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. 

Visit our website at http://www.emersonretailsolutions.com/ for the latest technical documentation and updates.

C O M P U T E R  P R O C E S S  C O N T R O L S

®

Installation Instructions: Wall-Mount 

Dewpoint Probe (210-2006)

The Wall-Mount Dewpoint Probe (

P/N 210-2006

) measures dewpoint for indoor applications such as 

anti-sweat heater control and HVAC dehumidification. The sensor’s linear 0-5VDC output makes the 
sensor compatible with the E2 site controller and all legacy CPC site control products that use MultiFlex 
and 16AI input boards.

Specifications

Mounting

Mount the dewpoint probe enclosure against a flat surface (such as a wall or riser) or junction box. 
Remove the front cover, and remove the two screws that attach the sensor’s circuit board to the rear 
mounting plate (

Figure 2

). Attach the mounting plate to the mounting surface (

Figure 3

), then reattach 

the circuit board and snap the cover back in place.

Property

Description/Value

Property

Description/Value

Operating Temperature

-5°C — 55°C (-23°F — 131°F)

Relative Humidity Range

0-95% RH

Storage Temperature

-40°C — 80°C (-40°F — 176°F)

Accuracy

+/- 1.2°C (+/- 3.6°F)

Supply Voltage

12-35VDC or 24VAC

Output Voltage

0-5VDC

Current consumption

12mA, maximum

External Load

R

L

 min. 10k

1.3"

(33 mm)

3.35"

(85 mm)

4.33"

(110 mm)

DEWPOINT ENCLOSURE DIMENSIONS

(WITH COVER ATTACHED)

REMOVE
SCREWS

3.

29"

(83.

5 mm)

2.49"

(63.3 mm)

0.23" (6 mm)

0.23" (6 mm)

0.23" (6 mm)

O0.16" (4.2mm)

Figure 1 - Enclosure Dimensions

Figure 2 - Circuit Board

Figure 3 - Mounting Plate Dimensions