technical bulletin
Document Part # 026-4824 Rev 0 5/8/2007
Page 1 of 2
©2007 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonretailsolutions.com/ for the latest technical documentation and updates.
C O M P U T E R P R O C E S S C O N T R O L S
®
Installation Instructions: Wall-Mount
Dewpoint Probe (210-2006)
The Wall-Mount Dewpoint Probe (
P/N 210-2006
) measures dewpoint for indoor applications such as
anti-sweat heater control and HVAC dehumidification. The sensor’s linear 0-5VDC output makes the
sensor compatible with the E2 site controller and all legacy CPC site control products that use MultiFlex
and 16AI input boards.
Specifications
Mounting
Mount the dewpoint probe enclosure against a flat surface (such as a wall or riser) or junction box.
Remove the front cover, and remove the two screws that attach the sensor’s circuit board to the rear
mounting plate (
Figure 2
). Attach the mounting plate to the mounting surface (
Figure 3
), then reattach
the circuit board and snap the cover back in place.
Property
Description/Value
Property
Description/Value
Operating Temperature
-5°C — 55°C (-23°F — 131°F)
Relative Humidity Range
0-95% RH
Storage Temperature
-40°C — 80°C (-40°F — 176°F)
Accuracy
+/- 1.2°C (+/- 3.6°F)
Supply Voltage
12-35VDC or 24VAC
Output Voltage
0-5VDC
Current consumption
12mA, maximum
External Load
R
L
min. 10k
Ω
1.3"
(33 mm)
3.35"
(85 mm)
4.33"
(110 mm)
DEWPOINT ENCLOSURE DIMENSIONS
(WITH COVER ATTACHED)
REMOVE
SCREWS
3.
29"
(83.
5 mm)
2.49"
(63.3 mm)
0.23" (6 mm)
0.23" (6 mm)
0.23" (6 mm)
O0.16" (4.2mm)
Figure 1 - Enclosure Dimensions
Figure 2 - Circuit Board
Figure 3 - Mounting Plate Dimensions