TECHNICAL BULLETIN

Part #: 026-4800  Revision 0  Date: 09/13/2000

COMPUTER PROCESS CONTROLS - http://www.cpcus.com/

Page 1

New CPC Humidity Sensor Installation Instructions

Overview

CPC is supplying a new relative humidity (RH) sensor model (P/N 203-5850) to replace the sen-
sor previously supplied with its REFLECS and Einstein controls system products (P/N 203-5850)
The new model is functionally identical to the previous RH sensor model with the same +0-5VDC 
output signal, but with distinct differences in the way it must be mounted and wired.

Mounting

The dimensions of the sensor are 4½” x 2¾”. To mount the sensor, pull the front cover from the 
rear mounting plate of the sensor. Using the two mounting holes on the mounting plate, screw the 
plate against a flat surface such as a wall or column. The sensor may also be mounted to a stan-
dard electrical wiring box. Make sure the plate is mounted so that the orientation arrow on the left 
side of the mounting plate points UP (refer to picture on the reverse side of this page).

When used indoors, mount the sensor in a central location within the zone to be measured, away 
from doors, windows, vents, heaters, and outside walls that could affect temperature readings. 
The sensor should be at least four feet from the floor, and no higher than necessary to prevent 
tampering.

Wiring

Cable Type

The cable type used to connect the humidity sensor with the CPC input board is Belden #8771 
(shielded, 3-conductor 22AWG).

Wire Connections

Connect the sensor cable from the five-pin connector on the RH sensor’s mounting plate to a 
point on a CPC 16AI input board or equivalent.

1.

Connect the RED (power) wire from sensor terminal #5 to one of the +12VDC supply terminals on the 
16AI.

2.

Connect the BLACK (ground) wire from sensor terminal #3 to the ODD-NUMBERED terminal of the 16AI 
point to which you want to connect the sensor.

3.

Clip the BARE (shield) wire at the sensor end of the cable. On the 16AI end of the cable, connect the BARE 
wire to the same ODD-NUMBERED terminal you connected the BLACK wire to in step 2.

4.

Connect the WHITE (signal) wire from sensor terminal #1 to the EVEN-NUMBERED terminal of the 16AI 
point to which you want to connect the sensor.