1

We reserve the right to make changes without notice

COSTER

TEMPERATURE AND HUMIDITY CONTROLLER
FOR TWO-BATTERY AIR HANDLING UNIT

DTU 644

   Eng.  C2

• Temperature and relative humidity control in air handling units
• Communication systems:

– telemanagement C-Bus

• Power supply 24 V~ , DIN rail mounting

1. APPLICATION

DTU 644 is designed for temperature and humidity control in air handling units composed of:

• 2 hot/chilled water or vapor batteries with 3-wire modulating control

or electric batteries with 1-,2-, or 3-stage On-Off control
or direct expansion batteries with 1-  or 2-stage On-Off control

• 1 adiabatic humidifying unit with On-off control

or

vapor-operated, with 3-wire modulating control, or 1- or 2-stage On-Off co

or

vapor-operated, with 0...10 V– control (alternative to air damper control)

•  1 air mixing unit with 0...10 V- air damper actuators

or 1 heat recuperator with 0...10 V- or On-Off control (CSV 304 converter).

The equipment can be included in a Telemanagement system through the C-Bus connection.

2. FEATURES

The main features of DTU 644 are as follows:

• Three 3-wire modulating outputs or 2-stage On-off (two equal loads) or 3-stage (two unequal loads) outputs,

configurable for:
– room temperature control (heating or cooling) with summer external compensation if desired, minimum

and maximum flow limits to prevent cold drafts, hot air stratification and condensing in the air ducts.

– flow temperature control (heating or cooling) with winter and summer compensation if desired
– pre-heating temperature control at variable values according to room temperature and humidity
– room relative humidity control – humidifying (flow limits, alternative to enthalpic comparison, if desired) and

dehumidifying

• 1   0...10 V– progressive output, configurable for:

–  air mixing control based on temperature or enthalpic comparison, with minimum external air limit
– external air control for room dehumidification with compensation of dew temperature on glass windows and

with minimum external air limit

– heat recuperator On-Off control according to room-external temperature comparison
– vapor-operated humidifier setting by means of a 0...10 V–  control

• Manual or automatic controller function seasonal switching.
• Remote-controlled temperature and humidity setting adjustment
• Alarms for short and open detector circuits and for system and equipment malfunction.

C     BUS

3. ACCESSORIES

No.

Description

Type

Application range

Sensing

Code

Data

element t

°

sheet

1

Duct flow air temperature detector

STA 010

0…60 

°

C

NTC 10 k

B1

1

Duct  outside air temperature detector

STA 001

–30…+40 

°

C

NTC 1 k

B2

or

wall  outside air temperature detector

SAE 001

–30…+40 

°

C

NTC 1 k

B2

1

Duct extract air temperature detector

STA 010

0…40 

°

C

NTC 10 k

B3

or

or room  air temperature detector

SAB 010

0…40 

°

C

NTC 10 k

B3

1

Duct pre-heating temperature detector

STA 010

0…40 

°

C

NTC 10 k

B4

or

duct relative humidity detector

STV 010

0…40 

°

C

NTC 10 k

B4

1

Room relative humidity and temperature detector

SAU 012

0…40 

°

C ; 20…80 %

NTC 10 k

B3-B6

or duct relative humidity detector

SUR 012

20…80 %

B6-B7

or duct relative humidity detector (swimming pools)

SUR 051

10…90 %

B6-B7

1

0...10 V–  to 2-stage On-Off Duct converter

CSV 304

U1

1

Modulating to 0...10 V– converter

CSC 304

U2

1

Temperature set-point adjuster

CDB 100

Rt

°

1

Relative humidity set-point adjuster

CDB 200

RH

1

Outside air minimum distance positioner

PCS 04

Rs

E 122

05.05.01

Содержание DTU 644

Страница 1: ...humidity control humidifying flow limits alternative to enthalpic comparison if desired and dehumidifying 1 0 10 V progressive output configurable for air mixing control based on temperature or enthalpic comparison with minimum external air limit external air control for room dehumidification with compensation of dew temperature on glass windows and with minimum external air limit heat recuperator...

Страница 2: ... 1 Alphanumeric display 2 and operating keys 3 and operating keys 4 Y1 output LED 5 Y2 output LED 1 2 3 3 4 5 1 Electronic component protection cover 2 Support base with transformer relays and terminal boards 3 Screws for securing cover to base 4 DIN rail securing elements 5 DIN rail release lever Dewpoint B4 Pb room heat x 0 5 1 20 Air dampers B2 B3 Pb room heat x 0 5 1 20 Aux heating B3 Pb room ...

Страница 3: ... 6 8 10 7 1 3 Wire Modulating Valve Control 5 6 7 8 9 10 1º 2º N L Y3 e 7 2 Electric Battery or Electric Humidifier Control Y 2 STAGES M2 6 8 10 7 4 Adiabatic Humidifier Of Off Control 2 equal loads Y 3 STAGES M2 6 8 10 Y 2 STAGES M2 6 8 10 7 3 Direct Expansion Battery Control Y3 MODULAT I NG Run t ime x x xs M2 10 Y3 2 STAGES M2 10 2 unequal loads Y1 2 c Direct expansion batteries refrigerators o...

Страница 4: ...l away from windows doors and sources of heat no alcoves scaffolds or hangings STA 010 extract air It should be installed upstream with respect to the extract fan 9 5 Duct mounting humidity detector B6 Extract air It must be installed upstream with respect to the extract fan Discharge air It should be installed downstream with respect to the discharge fan 9 6 Preheating or swimming pool dew point ...

Страница 5: ...Send i ngA l a rms NO PassWTe l eman NO 10 COMMUNICATION 10 1 C Bus Telemanagement Communication for more detailed information please see Technical Sheet T 021 Through the C Bus output DTU 644 can be managed remotely two way data communication by means of one or more local PC s and or a remote central computer via telephone network From the PC s it is possible to view and or change the following d...

Страница 6: ... adjuster optional B1 Flow temp detector B2 Outside temperature detector for compensation only B6 Room or extract humidity detector Rt Temperature set point adjuster optional RH Humidity set point adjuster optional 11 2 Room temperature and humidity control with flow temperature and humidity limits 11 3 Flow temperature and room or flow humidity control De t ec t o r l ayou t 2 3 5 6 8 M2 1 De t e...

Страница 7: ...I F I CAT I ON M2 12 B1 Flow temp detector B3 Room or extract temp detector B4 Dew point temp detector optional B6 Room or extract humidity detector Rt Temperature set point adjuster optional RH Humidity set point adjuster optional Rs Outside air min distance positioner optional Y1 Heating modulating control Ys Progressive air damper control dehumidification Use de t ec t o r B4 DEW PO I NT M2 4 B...

Страница 8: ...ff control 13 1 1 Preheating modulating battery 1 Post heating modulating battery 1 Humidifying On Off unit 13 3 1 Heating modulating battery 1 Cooling modulating battery 1 Humidifying On Off unit B1 Flow temp detector B2 Outside temp detector for compensation B3 Room or extract temp detector B6 Room or extract humidity detector Rt Temperature set point adjuster optional RH Humidity set point adju...

Страница 9: ...2 10 Y3 Wi n HUMI D I F Y3 Sum OFF M2 11 Se ason Sw i t ch i ng XXXXXXXXX M2 2 13 6 1 Winter heating summer cooling dehumidifying modulating battery 1 Summer post heating On Off battery 1 Humidifying On Off unit B1 Flow temp detector B2 Outside temp detector for compensation B3 Room or extract temp detector B6 Room or extract humidity detector Rt Temperature set point adjuster optional RH Humidity...

Страница 10: ... Wi n HEAT I NG Y1 Sum COOL DHU M2 7 Y2 2 STAGES M2 8 Y2 Wi n OFF Y2 Sum HEAT I NG M2 9 Y3 Wi n HUMI D I F Y3 Sum OFF M2 11 Sea son Swi t ch i ng XXXXXXXXX M2 2 Ou t pu t 8 9 1 0 CONTROL SEASON M2 3 13 9 1 Winter preheating summer cooling dehumidifying modulating battery 1 Winter post heating On Off battery 1 Summer post heating On Off battery 1 Humidifying On Off unit B1 Flow temp detector B2 Out...

Страница 11: ...idifying On Off unit B1 Flow temp detector B2 Outside temp detector for compensation B3 Room or extract temp detector B4 Preheating temperature detector B6 Room or extract humidity detector F Battery frost protection thermostat Y1 Winter preheating modulating control Y2 Summer cooling dehumidifying modulating control Y3 Post heating modulating control Rt Temperature set point adjuster optional RH ...

Страница 12: ...ry frost protection detector Mv Fan On Off control Y1 Winter preheating modulating control Y2 Summer cooling dehumidifying modulating control Y3 Post heating modulating control Mu Humidifier On Off control Rt Temperature set point adjuster optional RH Dehumidification set point adjuster optional De t ec t o r s La you t 6 7 8 M3 1 De t e c t o r s Layou t 1 2 3 4 5 6 M2 1 Y1 MODULAT I NG Run t ime...

Страница 13: ...ional RH Dehumidification set point adjuster optional De t e c t o r La you t 7 8 M3 1 De t e c t o r s La you t 1 2 3 5 6 M2 1 Y1 Wi n PREHEAT Y1 Sum COOL DHU M2 7 Y2 Wi n HEAT I NG Y2 Sum OFF M2 9 Y3 Wi n OFF Y3 Sum HEAT I NG M2 11 Season Sw i t ch i ng DA COMANDO c s M2 2 Y MODULAT I NG Run t ime x xxs M3 4 Y Wi n FROSTPROT Y Sum OFF M3 5 Use de t e c t o r B4 PREHEAT I NG M2 4 Ou t pu t 8 9 1 ...

Страница 14: ...peratures Desired temperatures for heating and cooling Can be set in and if B3 or B1 and B3 connected or in and if only B1connected If the set point adjuster Rt is connected these values can be changed remotely The value of the change is displayed in C next to the set values 16 2 Proportional band and Integral Time Basic temperature control parameters Proportional Band and Integral Time apply to h...

Страница 15: ... c Cooling flow temp min and max values determine the PbCoo proportional band s range The controller compares desired flow temperatures for Heating T fHea and for Cooling T fCoo and for Cooling T fCoo against the temperature measured by the discharge air detector B1and derives the load values for Heating Qhea and for Cooling Qcoo according to the deviations detected To prevent hot air stratificati...

Страница 16: ... D E1 is closed when contact c1 D E1 is open With with contact ss in winter D E1 closed mode is when contact c1 D E1 is closed when contact c1 D E1 is open With with contact ss in summer D E2 closed mode is when contact c1 D E2 is closed when contact c1 D E2 is open Cu r r en t mode ON Wi n t e r M0 2 Se ason Sw i t ch i ng XXXXXXXXX M2 2 Se ason Sw i t ch i ng NO M2 2 Cu r r en t mode ON M0 2 Cu ...

Страница 17: ...tings Heating Comp NO function disabled YES function enabled Opt xx c default outside temp summer Fpt xx c default flow temp summer 17 2 Summer compensation of desired room Cooling temperature This function can be only used if detectors B2 and B3 or B1 B2 and B3 are connected It is useful to prevent excessive temp differences between room and outside The controller maintains temp at a constant lev...

Страница 18: ...tector B7 is not being used for enthalpic comparison air damper control such detector can be employed as Humidification flow limit Min Max Min and max value of Humidification flow humidity When the value of flow humidity exceeds one of the limit values the desired Humidification value is increased or decreased by the set Influence value for each deviation The adjustment value is displayed in 18 2 ...

Страница 19: ...appliable The controller compares dew point temp T dp with the temp measured by detector B4 and calculates the reduction of the value requested for Dehumidification H Dehu according to deviation detected P r ehea t i ng T Mi n imum 1 0 0c M0 11 Dewpo i n t T Mi n imum 1 0 0c M0 11 P r ehe a t i ng T Ca l c 16 0c 0 0 M0 12 Dewpo i n t T Ca l c 1 6 0c 0 0 M0 12 Dehumi d i f i c a t i on Compensa t 0...

Страница 20: ...AGES 2 stage On Off control 1 2 1 2 for 2 unequal load electric batteries Stroke time xxx s valve actuator stroke time It only appears if control is MODULATING Each output can be assigned a different action load E g Y1 Heating If Season Switching is enabled in M2 2 a different action can be assigned for each season E g Y1 Win Heating Y1 Sum Cooling Y1 PREHEAT Preheating HEATING Heating AUX HEAT He...

Страница 21: ...r shuts outside air with a modulating action 22 7 Minimum outside air In the cases shown The minimum amount of outside air required to ensure air circulation can be controlled in two different ways directly through the controller display or using a minimum air positioner Rs directly connected to the air damper actuator 22 8 Rapid function In the cases shown If the Rapid Function is enabled when th...

Страница 22: ...nected When outside temp remains lower than For a period exceeding The controller switches the action of outputs Y1 Y2 Y3 and season control Ysc to Winter When outside temp remains lower than For a period exceeding The controller switches the action of outputs Y1 Y2 Y3 and season control Ysc to Summer Automatic season switching according to room temp only if B3 is connected When Heating load value...

Страница 23: ... only if B2 B3 B6 and B7 are connected and M2 12 reads DAMPENTHALPY Preheating desired and actual temperature only if B4 is connected and Dew point desired and actual temperature only if B4 is connected and Output Y1 load value Preheat or Heat or AuxHea or Ht P Hea or Cool or Cool Dehu Output Y2 load value Preheat or Heat or AuxHea or Ht P Hea or Cool or Cool Dehu Output Y3 load value Humid or Hea...

Страница 24: ...s occur when there is a continuing deviation between actual and desired measures These alarms do not affect the controller s proper operation Non pregiudicano il regolare funzionamento del regolatore By default all alarms are disabled except clock alarm 8 Use the and keys to enable desired alarms entering numbers in place of the dashes Number flashing the alarm is on Alarm limit values and delays ...

Страница 25: ...H 50 M0 TECHN I CAL PAGES PRESS KEY DTU 6 44 C2 Eng Ve r s xx BST F r 26 0 3 t o 2 8 10 12 18 MONDAY 10 03 0 0 GMT Y3 Humi d i f 100 Ys Damp en t 100 Y1 Hea t i ng 1 00 Y2 Coo l i ng 1 00 Des P r he a t 1 5 0c Ac t P r he a t 1 5 0c Room 6 5K j Kg Ou t 4 4K j Kg Ou t s i deT 2 0c Ou t Humi d 5 0 Ac t ua l f l ow Tempe r a t 3 5 0c Ca l cu l a t ed F l ow Coo l i ng 3 5 0c Ca l cu l a t ed F l ow H...

Страница 26: ...r ehea t i ng T Ca l c 16 0 c 0 0 M0 12 Preheating or Dew Point temperature calculated temp Manual adjustment of calculated value 19 1 2 Displayed if B4 is connected and if M2 4 setting is PREHEATING Displayed if B4 is connected and if M2 4 setting is DEWPOINT Dewpo i n t T Ca l c 16 0 c 0 0 Ca l cu l a t ed F l ow Hea t i ng T 22 0c M0 13 Calculated flow temperature based on Heating control 24 3 ...

Страница 27: ...roject temp 17 1 Displayed if B1 and B2 are connected and B3 is not connected Summer Compen NO D i f f O T R T 6c M1 10 Summer compensation NO YES Differ O T R T maximum allowed difference between summer outside temp and desired temp above which desired temp is increased by 1 C for each C increase in outside temp 17 2 Displayed if B2 and B3 or B1 B2 and B3 are connected Re l a t i veHumi d i t y P...

Страница 28: ...OLING COOL DHU OFF 21 Y2 Wi n COOL I NG Y2 Sum COOL I NG Action of output Y2 in season switching Displayed if M2 2 setting is not NO Output Y3 MODULATING 2 STAGES 3 STAGES Actuator stroke time in seconds M2 10 Displayed only if M2 3 setting is CONTROL Stroke time displayed only if MODULATING 21 Y3 MODULAT I NG Tempo Co r sa 120s Output Y3 action Displayed if M2 2 setting is NO Y3 HUMI D I F M2 11 ...

Страница 29: ...3 are connected Ou t pu t Y1 MODUL S t a t us I DLE M3 1 Select outputs to be tested Select output status 26 Output selection Y1 MODUL or Y1 2 STAGES or Y1 3 STAGES Y2 MODUL or Y2 2 STAGES or Y2 3 STAGES Y3 MODUL or Y3 2 STAGES or Y3 3 STAGES Ycs Ys Status selection With Y MODUL IDLE CLOSE OPEN With Y 2 STAGES ON 1 ON 1 2 OFF With Y 3 STAGES ON 1 ON 2 ON 1 2 OFF With Ycs WINTER SUMMER With Ys 0 VO...

Страница 30: ...30 E 122 DTU 644 C2 Eng 05 05 01 We reserve the right to make changes without notice COSTER ...

Страница 31: ...31 We reserve the right to make changes without notice COSTER ...

Страница 32: ...ert n 9115 COEE Head Office Sales Tel 39 02 2722121 TI Tel 39 02 45476193 FW Fax 39 02 2593645 Reg Off Central Southern Tel 39 06 5573330 Fax 39 06 5566517 Orders and Shipping Tel 39 0364 7732 00 02 Fax 39 0364 770016 E mail info coster info 20132 Milan Via San G B De La Salle 4 a 00146 Rome Viale G Marconi 437 25048 Edolo BS Via Gen Treboldi 190 192 Web www coster info ...

Отзывы: