1
B 268 - XSE 602 C1 Eng.
22.11.10 AM
REV. 02
We reserve the right to make changes witout notice
COSTER
B 268
22.11.10 AM
REV. 02
SLAVE OPTIMISING COMPENSATOR
FOR CONTROL TWO ZONES
XSE 602
C1
Eng.
• Slave optimising compensator
for two zones
– functions only if connected in C-Ring with a "PRIMARY" controller
• Communication systems :
–
C-Ring
for exchanging data between local controllers.
– C-Bus
: XSE 602 Telemanagement optional;
to enable Telemanagement use the “"
C-Bus Plug-in" type ACB 400 C1 or later
,
to be ordered separately as accessory
• Power supply 230 V AC (or 240 for UK market) ; DIN rail mounting
1. APPLICATION
XSE 602 controller can function only if connected in C-Ring with a "Primary" controller and is able to exchange data
of common interest with other controllers.
XSE 602 is designed for compensated/optimised control of two heating zones in :
– commercial and public buildings
– schools
– residential complexes
By means of C-Bus interface it can be inserted in a telemanagement system.
2. FUNCTIONS
The principal functions of XSE 602 are :
• Compensated control of two heating zones by three-wire control of valves :
– optimisation of start and stop times of plants
– control of plant pumps (with delay in switching off) according current programme of event times
– minimum and maximum temperature limits of flows
– correction of heating curve origin
– self-adjusting
– Eco Off
• Timed programming: twentyfive 24Hour programs & two 7Day periods
• Programming with dates : twentyfive holiday periods ; winter season ; special period.
• Summer plant exercise of valves and pumps
• Automatic change GMT / BST
• Metering of degree-days
• Remote control for modifying current timed programme of events
• Three On-Off inputs for signalling status or alarm
• Alarms for detector short or open circuits and for irregular operation of plants and components
• C-Ring connection for exchange of data with other local controllers
• C-Bus connection for exchange data with local PCs or remote telemangement PC
• Optional C-Bus transmission of data with local PCs or remote Telemanagement PC.
To enable data transmission and Telemanagement use the “C-Bus Plug-in” type ACB 400 C1 or later
To communicate locally with a PC use the test Plug-in type ACX 232
3. DETECTORS, REMOTE CONTROLS & ACCESSORIES
No.
Description
Type
Sensing
Code
Data
element
sheet
1
Heating flow surface
(1)
temperature detector
SCH 010
NTC 10 k
Ω
B1-B5
N 130
1
Outside temperature detector
SAE 001
NTC 1k
Ω
B2
N 120
Accessories :
1
Ambient temperature detector
SAB 010
NTC 10 k
Ω
B3-B6
N 111
1
Boiler anticondensing immersion detector
SIH 010
NTC 10 k
Ω
B4
N 140
1
Remote control for modifying current programme
CDB 300
–
R
–
Options :
1
1) Immersion temperature detector
SIH 010
NTC 10 k
Ω
B1-B5
N 140
Accessory for Telemanagement
1
Plug-in for communicating via C-Bus
ACB 400C1
–
–
T 433
C RING
BUS
C
OPTIONAL