4 Series and Parallel

 Operation

4.1  Series operation

¡

Series operation is available by connecting the outputs of two or 
more power supplies as shown below.  Output current in series 
connection should be lower than the lowest rated current in each 
unit.

Load

Load

Power

Supply

Power

Supply

Load

Power

Supply

Power

Supply

(a)

(b)

Fig.4.1 Examples of series operation

4.2  Parallel operation

¡

Parallel operation is not possible.

¡

Redundancy operation is available by wiring as shown below.

Power

Supply

Power

Supply

Load

I

I

1

I

3

2

Fig.4.2  Example of Redundancy Operation

¡

Even a slight difference in output voltage can affect the balance 
between the values of I

1

 and I

2

.

Please make sure that the value of I

3

 does not exceed the rated 

current of a power supply. 

I

3

   the rated current value

4.3  Various connection methods

¡

Using one smoothing capacitor, up to two TUHS can be operated. 
Shown an example in Fig.4.3.

¡

Total output wattage must be less than the maximum wattage of 
TUHS which AC is supplied.

¡

When connect different wattage of TUHS, please input AC into the 
power supply which the wattage is higher.

¡

When smoothing capacitor is commonly used, noise may become 
big because of the length of the power line. The noise can be 
attenuate by connecting Line Filter between TUHS and R1.

¡

Avoid connecting AC input and DC input at the same time because 
it may damage the TUHS or an equipment(Fig.4.4).

+Vout

+BC

AC1

AC2

-BC -Vout

F1

R1

Load

+

Cbc

+Vout

+BC

AC1

AC2

-BC -Vout

F1 D1

Load

+

Cbc

+Vout

+BC

AC1

AC2

-BC

-Vout

Load

+Vout

+BC

AC1

AC2

-BC

-Vout

Load

SK1

C1(TUHS25)

(a) AC input , Cbc common 

(b) DC input , Cbc common

Fig.4.3 TUHS connect method

SK1

+Vout

+BC

AC1

AC2

-BC

-Vout

F1

R1

Load

+

Cbc

Fig.4.4 TUHS Connection prohibition

4.4  Long hold-up time connection

¡

It is possible that setting the hold-up time of the power supply for a 
long time by connecting like Fig.5.5. Please set the charge current 
of the CL to become less than 1A. Please use the diode which 
reverse voltage is 600V or more.Please contact us for detail.

F1

R1

+Vout

+BC

AC1

AC2

-BC

-Vout

D

L

R

L

Load

+

Cbc

C

L

SK1

C1(TUHS25)

+

Fig.4.5 Long hold-up time connection

AC-DC Power Supplies PCB Mount Type

Instruction Manual

TUHS-19

June 26, 2020