1 Function

1.1 Input voltage range

 

¡

The range is from AC85V to AC264V or DC120V to DC370V 

(please see SPECIFICATIONS for details).

¡

In cases that conform with safety standard, input voltage range is 
AC100-AC240V (50/60Hz).

¡

If input value doesn’t fall within above range, a unit may not operate in 
accordance with specifications and/or start output voltage hunting or fail.
If you need to apply a square waveform input voltage, which is 
commonly used in UPS and inverters, please contact us.

¡

When the input voltage changes suddenly, the output voltage ac-
curacy might exceed the specification. Please contact us.

¡

Operation stop voltage is set at a lower value than that of a stan-
dard version (derating is needed).

 

-

Use Conditions

Output

LFP100F

30W

LFP150F

50W

LFP240F

80W

LFP300F

100W

Input  AC50V or DC70V

Duty 1s/30s

1.2 Inrush current limiting

¡

An inrush current limiting circuit is built-in.

¡

If you need to use a switch on the input side, please select one 
that can withstand an input inrush current.

¿ 

LFP100F, LFP150F

¡

Thermistor is used in the inrush current limiting circuit.  When you 
turn the power ON/OFF repeatedly within a short period of time, 
please have enough intervals so that a power supply cools down 
before being turned on.

¿ 

LFP240F, LFP300F

¡

Thyristor technique is used in the inrush current limiting circuit. 
When you turn power ON/OFF repeatedly within a short period of 
time, please have enough intervals so that the inrush current limit-
ing circuit becomes operative.

¡

When the switch of the input is turned on, the primary inrush cur-
rent and secondary inrush current will be generated because the 
thyristor technique is used for the inrush current limiting circuit.

1.3 Overcurrent protection

¡

An overcurrent protection circuit is built-in and activated over 

101% of the peak current. A unit automatically recovers when a 
fault condition is removed.
Please do not use a unit in short circuit and/or under an overcur-
rent condition.

¡

Hiccup Operation Mode
Hiccup operation for overcurrent protection is included in a part of 
series. When the overcurrent protection circuit is activated and the 
output voltage drops to a certain extent, the output becomes hic-
cup so that the average current will also decrease.

1.4 Overvoltage protection

¡

An overvoltage protection circuit is built-in.  If the overvoltage pro-
tection circuit is activated, shut down the input voltage, wait more 
than 3 minutes and turn on the AC input again to recover the out-
put voltage.  Recovery time varies depending on such factors as 
input voltage value at the time of the operation.

¡

In option -R2, overvoltage protection is removed by toggling ON/
OFF signal of remote control. 

Remarks :

 

Please avoid applying a voltage exceeding the rated voltage to an 
output terminal.  Doing so may cause a power supply to malfunc-
tion or fail.  If you cannot avoid doing so, for example, if you need 
to operate a motor, etc., please install an external diode on the 
output terminal to protect the unit.

1.5 Thermal protection

¡

A thermal protection circuit is built-in.

  The thermal protection circuit may be activated under the follow-

ing conditions and shut down the output.

1

When a temperature continue to exceed the values determined 
by the derating curve.

2

When a current exceeding the rated current is applied.

3

When convection stops.

4

 When peak load is applied in conditions other than those shown  
in Section 5.

If the thermal protection circuit is activated, shut off the input volt-
age and eliminate all the overheating conditions.  To recover the 
output voltage, have enough time to cool down the unit before 
turning on the input voltage again.

1.6 Output voltage adjustment range

¡

Adjustment of output voltage is possible by using potentiometer. 

1.7 Output ripple and ripple noise

¡

Output ripple noise may be influenced by  measurement environ-
ment, measuring method fig.1.1 is recommended.

+Vout

-Vout

Load

150mm

C

2

C

1

Osiloscope/

Ripple noise meter

Bw:20MHz

Differential probe

+

C

1 : 

Film capacitor 0.1μF

C

2 : 

Aluminum electrolytic capacitor 22μF

Fig.1.1 Measuring method of Ripple and Ripple Noise

Remarks :

 

When GND cable of probe with flux of magnetic force from power 
supply are crossing, ripple and ripple noise might not measure 
correctly.

  Please note the measuring environment.

*

 Please avoid using continuously 
for more than 1 second under 
above conditions.  Doing so 
may cause a failure.

AC-DC Power Supplies Open Frame/ Enclosed Type

Instruction Manual

LFP-14

June 26, 2020

Содержание LFP100F

Страница 1: ...ge protection 1 5 Thermal protection 1 6 Output voltage adjustment range 1 7 Output ripple and ripple noise 1 8 Isolation 1 9 Reducing standby power LFP 13 LFP 13 LFP 13 LFP 13 LFP 13 LFP 13 LFP 13 LF...

Страница 2: ...drops to a certain extent the output becomes hic cup so that the average current will also decrease 1 4 Overvoltage protection An overvoltage protection circuit is built in If the overvoltage pro tec...

Страница 3: ...75 89 89 0 Io 50 89 89 C Convection 75 Io 100 85 86 50 Io 75 89 89 0 Io 50 89 89 D Convection 75 Io 100 84 76 50 Io 75 89 86 0 Io 50 89 89 E Convection 75 Io 100 81 89 50 Io 75 86 89 0 Io 50 87 89 F...

Страница 4: ...more 8years B Convection Ta 35C or less 10years or more 10years or more Ta 45C 10years or more 10years or more C Convection Ta 35C or less 10years or more 10years or more Ta 45C 10years or more 6years...

Страница 5: ...emperature year Warranty Io 75 75 Io 100 A Convection Ta 40C or less 5years 5years Ta 50C 5years 3years B Convection Ta 35C or less 5years 5years Ta 45C 5years 3years C Convection Ta 35C or less 5year...

Страница 6: ...dard untis Please contact us about the detail LFP300F I O Connector Mating connector Terminal CN1 7 1565036 6 1 1123722 8 Chain 1123721 1 Loose 1318912 1 CN2 1 1123723 6 1 1123722 6 Chain 1123721 1 Lo...

Страница 7: ...t limiting resistor R If the output exceeds 12 5V however please connect the cur rent limiting resistor R To calculate a current limiting resistance value please use the fol lowing equation R W Vcc 1...

Страница 8: ...cessary to use wires which rated voltage is 600V or more 4 It must be used with the external capacitor unit CR HUT 5 For more information about the external capacitor unit and har ness please refer to...

Отзывы: