background image

6   Applicable  Electric 

Cable

¡

Input terminals, Output terminals 

¿ 

KHEA30F/60F/90F/120F/240F

Table 6.1  Applicable Wire

Input  terminals

Output terminals

Solid wire

Diameter 0.5 mm to 2.6 mm (AWG.24 to AWG.10)

Stranded wire

0.2mm

2

 to 5.2mm

2

 (AWG.24 to AWG.10)

Conductor diameter more than 0.18mm

Sheath strip length

8mm

¿ 

KHEA480F

Table 6.2  Applicable Wire

Input  terminals

Output terminals

Solid wire

Diameter 0.8 mm to 2.6 mm (AWG.20 to AWG.10)

Stranded wire

0.5mm

2

 to 5.2mm

2

 (AWG.20 to AWG.10)

Conductor diameter more than 0.18mm

Sheath strip length

8mm

¡

RC terminals

¿ 

KHEA120F/240F/480F,

 KHNA120F/240F/480F

Table 6.3  Applicable Wire

RC terminals

Solid wire

Diameter 0.5 mm to 1.3 mm (AWG.24 to AWG.16)

Stranded wire

0.2 mm

2

 to 1.5 mm

(AWG.24 to AWG.16)

Sheath strip length

8mm

7  Option

7.1  Outline of option

¿ 

-C

-

Option -C models have coated internal PCB for better moisture 

resistance.

¿ 

-E

(KHEA90F, KHNA90F)

-

Option -E models acquires NEC Class2.

¿ 

-N2

(KHEA120F/240F/480F, KHNA120F/240F/480F)

-

Option -N2 models have attachment with screw mounting in-

stead of DIN rail mounting.

  Mounting holes pitch are shown in Table 7.1.

4-

f

4.5

B

A

Fig.7.1  Image of option -N2

Fig.7.2  Mounting place

   

(screw holes)

Table 7.1  Mounting holes pitch

No.

Model

A

B

1

KHEA120F, KHNA120F

23mm

133mm

2

KHEA240F, KHNA240F

34mm

133mm

3

KHEA480F, KHNA480F

54mm

133mm

7.2  Others

¡

While turning on the electricity, and for a while after turning off, 
please don’t touch the inside of a power supply because there are 

   some hot parts in that.

¡

When a mass capacitor is connected with the output terminal 
(load side), the output might become the stop or an unstable oper-
ation.  Please contact us for details when you connect the capaci- 
tor.

AC-DC Power Supplies DIN Rail Type

Instruction Manual

KH-29

June 29, 2020

Содержание KHEA120F

Страница 1: ...Signal Output 1 12 Derating for low temperature start up 2 Peak Current KH 24 3 Series Parallel Operation KH 24 4 Temperature Measurement Point KH 25 5 Life Expectancy and Warranty KH 26 6 Applicable...

Страница 2: ...d 1 3 Overcurrent Protection KHEA30F 60F 90F KHNA30F 60F 90F A overcurrent protection circuit is built in and activated over 105 of the rated current A unit automatically recovers when a fault conditi...

Страница 3: ...OFF 1 If the output of an external power supply is within the range of 4 5 29 5V you do not need a current limiting resistor R If the output exceeds 29 5V however please connect the current limit ing...

Страница 4: ...4V 3 Series Parallel Operation 3 1 Series Operation You can use a power supply in series operation The output cur rent in series operation should be lower than the rated current of a power supply with...

Страница 5: ...ement because POINT A and POINT B is live potential Fig 4 4 Temperature measurement point Forced air Table 4 1 Specified temperature of the measurement point No Model Temperature measurement point Poi...

Страница 6: ...B Convection AC85 170V Ta 30C or less 10years or more 8years Ta 40C 10years or more 3years AC170 264V Ta 45C or less 10years or more 7years Ta 55C 5years 3years C Convection AC85 170V Ta 40C or less...

Страница 7: ...Ta 30C 10years or more 8years AC170 264V Ta 40C or less 10years or more 9years Ta 50C 8years 4years A B C D and E Forced air AC85 264V Ta 70C 5years 3years Table 5 6 Life Expectancy KHEA480F KHNA480F...

Страница 8: ...rs 5years Ta 60C 5years 3years AC170 264V Ta 50C or less 5years 5years Ta 60C 5years 4years B Convection AC85 170V Ta 40C or less 5years 5years Ta 50C 5years 5years AC170 264V Ta 40C or less 5years 5y...

Страница 9: ...on 7 1 Outline of option C Option C models have coated internal PCB for better moisture resistance E KHEA90F KHNA90F Option E models acquires NEC Class2 N2 KHEA120F 240F 480F KHNA120F 240F 480F Option...

Отзывы: