1.1  Input Voltage Range

¡

Input voltage range of the power supplies is from AC85V to 

AC264V or DC (please see SPECIFICATIONS for details).

¡

If input value doesn’t fall within above range, a unit may not oper-
ate in accordance with specifications and/or start hunting or oper-
ate protection circuit or fail.

  If you need to apply a square waveform input voltage, which is 

commonly used in UPS and inverters, please contact us.

¡

When the input voltage changes suddenly, the output voltage    

accuracy might exceed the specification.  Please contact us.

¡

To comply with safety standards,input voltage range is shown in 
Table 1.1.

Table 1.1  Input voltage range of safety standards

No.

Series

Input Voltage range

AC input

DC input

1

KHEA30F, KHNA30F

100V-240V 

(50/60Hz)

88V-250V

2

KHEA60F, KHNA60F

3

KHEA90F, KHNA90F

4

KHEA120F, KHNA120F

88V-350V

5

KHEA240F, KHNA240F

6

KHEA480F, KHNA480F

¿ 

KHEA30F/60F/90F, KHNA30F/60F/90F

¡

Operation stop voltage is set at a lower value than of a standard 
version (derating is needed).

 

-

Use Conditions

 Output

KHEA30F,KHNA30F

10W

KHEA60F,KHNA60F

20W

KHEA90F,KHNA90F

30W

Input    AC50V or DC70V

Duty  1s/30s

*

Please avoid using continuously for more than 1 second under 

above conditions. Doing so may cause a failure.

1.2  Inrush Current Limiting

¡

An inrush current limiting circuit is built-in.

¡

If you need to use a switch on the input side, please select one 
that can withstand an input inrush current.

¿ 

KHEA30F/60F/90F/120F,

    KHNA30F/60F/90F/120F

¡

Thermistor is used in the inrush current limiting circuit. When you 
turn the power ON/OFF repeatedly within a short period of time, 
please have enough intervals so that a power supply cools down 
before being turned on.

¿ 

KHEA240F/480F, KHNA240F/480F

¡

Thyristor technique (KHEA/KHNA240F) and power relay tech-
nique (KHEA/KHNA480F) is used in the inrush current limiting 
circuit.

1 Functions

¡

When you turn the power ON/OFF repeatedly within a short period 
of time, please have enough intervals so that the inrush current 
limiting circuit becomes operative.

¡

When the switch of the input is turned on, the primary inrush cur-
rent and secondary inrush current will be generated.

1.3  Overcurrent Protection

¿ 

KHEA30F/60F/90F, KHNA30F/60F/90F

¡

A overcurrent protection circuit is built-in and activated over 105% 
of the rated current.  A unit automatically recovers when a fault 
condition is removed.  Please do not use a unit in short circuit and/
or under an overcurrent condition.

¡

Hiccup Operation Mode (except KHEA/KHNA90F)

  When the overcurrent protection circuit is activated and the output 

voltage drops to a certain extent, the output becomes hiccup so 
that the average current will also decrease.

¡

Output Voltage Shutdown

  If the output voltage drops according to the overcurrent protection 

circuit operating continuously for about 0.5 second, the output 
voltage may shut down.  To recover the output voltage, remove a 
condition that is causing an overcurrent, shut down the input volt-
age, wait more than 3 minutes and turn on the AC input again.

¿ 

KHEA120F/240F/480F, KHNA120F/240F/480F

¡

An overcurrent protection circuit is built-in and activated over 

101% of the peak current.  A unit automatically recovers when a 
fault condition is removed.  Please do not use a unit in short cir-
cuit and/or under an overcurrent condition.

¡

Hiccup Operation Mode

  When the overcurrent protection circuit is activated and the out-

putvoltage drops to a certain extent, the output becomes hiccup 
so that the average current will also decrease.

1.4  Peakcurrent Protection

¿ 

KHEA120F/240F/480F, KHNA120F/240F/480F

¡

Peakcurrent protection is built-in (refer to Instruction Manual 3 for 
Peak loading).

  If this function comes into effect, the output is shut down.
  A few seconds later, A unit automatically recovers.
  But if the overcurrent condition has not been released, the output 

will stop again (hiccup Operation Mode).

*

The recovery time varies depending on input voltage and load 

condition.

1.5  Overvoltage Protection

¿ 

KHEA30F/60F/90F, KHNA30F/60F/90F

¡

An overvoltage protection circuit is built-in. If the overvoltage pro-
tection circuit is activated, shut down the input voltage, wait more 
than 3 minutes and turn on the AC input again to recover the out-
put voltage. Recovery time varies depending on such factors as 
input  voltage value at the time of the operation.

¿ 

KHEA120F/240F/480F, KHNA120F/240F/480F

¡

An overvoltage protection circuit is built-in.

AC-DC Power Supplies DIN Rail Type

Instruction Manual

KH-22

June 29, 2020

Содержание KHEA120F

Страница 1: ...Signal Output 1 12 Derating for low temperature start up 2 Peak Current KH 24 3 Series Parallel Operation KH 24 4 Temperature Measurement Point KH 25 5 Life Expectancy and Warranty KH 26 6 Applicable...

Страница 2: ...d 1 3 Overcurrent Protection KHEA30F 60F 90F KHNA30F 60F 90F A overcurrent protection circuit is built in and activated over 105 of the rated current A unit automatically recovers when a fault conditi...

Страница 3: ...OFF 1 If the output of an external power supply is within the range of 4 5 29 5V you do not need a current limiting resistor R If the output exceeds 29 5V however please connect the current limit ing...

Страница 4: ...4V 3 Series Parallel Operation 3 1 Series Operation You can use a power supply in series operation The output cur rent in series operation should be lower than the rated current of a power supply with...

Страница 5: ...ement because POINT A and POINT B is live potential Fig 4 4 Temperature measurement point Forced air Table 4 1 Specified temperature of the measurement point No Model Temperature measurement point Poi...

Страница 6: ...B Convection AC85 170V Ta 30C or less 10years or more 8years Ta 40C 10years or more 3years AC170 264V Ta 45C or less 10years or more 7years Ta 55C 5years 3years C Convection AC85 170V Ta 40C or less...

Страница 7: ...Ta 30C 10years or more 8years AC170 264V Ta 40C or less 10years or more 9years Ta 50C 8years 4years A B C D and E Forced air AC85 264V Ta 70C 5years 3years Table 5 6 Life Expectancy KHEA480F KHNA480F...

Страница 8: ...rs 5years Ta 60C 5years 3years AC170 264V Ta 50C or less 5years 5years Ta 60C 5years 4years B Convection AC85 170V Ta 40C or less 5years 5years Ta 50C 5years 5years AC170 264V Ta 40C or less 5years 5y...

Страница 9: ...on 7 1 Outline of option C Option C models have coated internal PCB for better moisture resistance E KHEA90F KHNA90F Option E models acquires NEC Class2 N2 KHEA120F 240F 480F KHNA120F 240F 480F Option...

Отзывы: