Fault finding
Symptom
Probable cause
Action
Turbine speed
varies, it shuts down
and restarts again
The turbine is too heavily
loaded, the resistance
through the construction or
the hoses is too high due to
too few suction/pressure
points, squeezed or clogged
hoses, and/or clogged filter.
Inspect the installation and all filters, both
that of the turbine itself and the others in
the system. Verify that they are clean and
are not stopping the flow. Verify that no
hoses are squeezed or clogged with dirt.
Make and install additional suction or
pressure points depending on installation.
Drill further holes and connect additional
hoses or whatever is appropriate and feasible
to decrease the resistance and increase the
flow.
The turbine makes
noise, does not
sound the way it
normally does.
Bearing in motor is worn
and/or damaged.
Please contact your retailer for repair.
The turbine has
stopped/ does not
start.
No mains power.
Built-in overheating
protection triggered.
Turbine failure.
Check that power cable is connected and that
the power outlet is live, that the fuse and, if
present, the ground fault circuit breaker are
in order.
Disconnect power by pulling the cable from
the socket and let the turbine cool down for
15 minutes. Reconnect the power and start
the turbine.
If the above does not rectify the operation,
please contact your retailer for repair.
Содержание T2 ES
Страница 1: ...T2 ES T4 ES TURBINES USER MANUAL ...
Страница 2: ......
Страница 23: ...Interface Map for CTR A2ES CTR A4 ES and CTR A ES Top Menu ...
Страница 24: ...Sublevels Info Statistics Info Info Info Reset Reset Info ...
Страница 26: ...Create Activate Activate Deactivate OK Edit ...
Страница 27: ...Info Change ...