STANDARD RECOMMENDED PROCEDURE 000-274 | ISSUE 4 | AUgUST 2016 | PAgE 6 OF 7

Step 6: 

Beginning with adapter 12, mate six connectors into adapters 7 through 12 and route 

the fibers as shown in Figure 7.

Step 7: 

Then mate the last six connectors into adapters 1 through 6 and route the fibers as 

shown.

Figure 7

7.  Installing Cassettes

Step 1: 

Starting in the lower right corner of the housing as viewed from the rear (Figure 8), 

install the first cassette.

Step 2: 

Continue installing cassettes across the first row, then move to the next row, 

beginning again in the right corner. Strain-relieve cable sheath with cable tie as 

shown.

Step 3: 

Repeat Step 2 until all cassettes have been installed.

Step 4: 

If not already done, loosely install a hook-and-loop strap through the lance in the 

baseplate to organize and secure the fiber subunits as a single uniform bundle. Make 

sure to leave enough slack to allow the tray to be pulled out without stressing or 

exceeding the minimum bend radius of the cable.

Figure 8

TPA-4383

Route fibers 7 through 12

Then route fibers 1 through 6

After splicing inside the

cassette, insert cassette 

in first row, installing from 

right to left across each row.

1

TPA-4385

Strain-relieve cable sheath with 4-inch cable tie to baseplate

where it enters the housing. Loosely secure legs with hook-

and-loop strap to lance in center of baseplate.

2

Содержание EDGE Splice Cassette

Страница 1: ...t resistant safety gloves to protect your hands from accidental injury when using sharp bladed tools and armored cable is strongly recommended Use extreme care when working with severed armor There will be a sharp edge where armor is cut To minimize the chance of injury from the cut armor cover the exposed edge with a wrap of electrical tape To minimize the chance of injury from sharp bladed tools...

Страница 2: ...be carrying laser light Laser light can be invisible and can damage your eyes Viewing it directly does not cause pain The iris of the eye will not close involuntarily as when viewing a bright light Consequently serious damage to the retina of the eye is possible Should accidental eye exposure to laser light be suspected arrange for an eye examination immediately CAUTION Cleaved or broken glass fib...

Страница 3: ... shown in Figure 4 storing fibers under the flanges to prevent them from being pinched when reinstalling the cover It will be necessary to twist the fibers and flip them over to neatly route them inside the cassette Figure 4 Step 6 Insert all spliced protectors into the organizer NOTE 1 If de ribbonizing is required for splicing single fiber splicing refer to Corning Optical Communications Standar...

Страница 4: ...N Cleaved or broken glass fibers are very sharp and can pierce the skin easily Do not let these pieces of fiber stick to your clothing or drop in the work area where they can cause injury later Use tweezers to pick up cleaved or broken pieces of glass fibers and place them on a loop of tape kept for that purpose alone Good housekeeping is very important BL X BL OR X OR gR X gR BR X BR SL X SL WH X...

Страница 5: ...llation use the EMOD CP12 xx product instead For easier fiber routing during field termination within the EDGE field terminated cassette Corning strongly advises that connector boots NOT be used Additionally connector clips triggers should NOT be used within the EDGE field terminated cassette When using 250 µm fiber use a short section of 900 µm tubing instead of a connector boot immediately behin...

Страница 6: ...ieve cable sheath with cable tie as shown Step 3 Repeat Step 2 until all cassettes have been installed Step 4 If not already done loosely install a hook and loop strap through the lance in the baseplate to organize and secure the fiber subunits as a single uniform bundle Make sure to leave enough slack to allow the tray to be pulled out without stressing or exceeding the minimum bend radius of the...

Страница 7: ...able at www corning com opcomm trademarks All other trademarks are the properties of their respective owners Corning Optical Communications is ISO 9001 certified 2013 2016 Corning Optical Communications All rights reserved 8 Secure the Housing Step 1 Close the rear door and ensure the latches are engaged Step 2 From the front of the housing open the door and pull the housing trays out to ensure ad...

Отзывы: