background image

5

166240010

INSTALLATION INSTRUCTIONS

You will get better service from the ice machine, longer life and greater convenience if you choose its location

with care.

Here are a few points to consider:

1. Select a location as close as possible to where you are going to use the ice.

2. Allow a minimum of 6”space at sides and rear of machine for ventilation.

3. A kitchen installation is not desirable as a rule. If a kitchen installation is necessary, locate the machine as

far away

from the cooking area as possible. Grease laden air will form greasy deposits on the condenser. This re-

duces the ice making efficiency and necessitates thorough cleaning quite often.

4. If you install the unit in a storeroom, be sure the room is well ventilated.

NOTE:

Do not install where the ambient and incoming water temperature will drop below 50

°

F or rise to

over 100

°

F.

NOTE:

If water pressure exceeds 50 lbs., a water pressure regulator should be installed in water inlet

line between water shut- off valve and strainer. Minimum incoming water pressure required is 22 lbs..

A. Uncrate the unit by removing the staples or nails from the bottom of the carton and lift off.

B. Remove the bolts holding the skid to the machine.

C. If legs are used, adjust the leveling legs of the storage bin until the unit is level and all four (4) legs are

in solid contact with the floor. Leveling is very important to obtain proper draining

.

D. Provide a cold water supply line to the area selected for the installation of the unit. The incoming wa-

ter line should have a shut--off valve provided at a convenient location close to the ice maker. The wa-

ter strainer provided with the unit should be installed on the down--stream side of the shut--off valve.

The supply line must be adequately sized to compensate for the lengths of the incoming water run.

The machine is equipped with a 3/8”male flare connection for the incoming water line.

NOTE:

ALWAYS FLUSH OUT WATER LINES BEFORE STARTING UNIT.

Water cooled units have a water regulating valve that is factory set to operate at 270 to 310 PSIG

head pressure for R404a (water outlet temp. approx. 105F) This should be checked at the time the

unit is being installed.

Two water inlet connections are provided on water cooled units, one for the ice making (evaporator)

section, the other is for the water cooled condenser. Both connections are 3/8”male flare fittings. In-

let water to the condenser will go to the water regulating valve first, then to the condenser coil and out

the drain.

The reason for separate water inlet connections is that some installations use a water tower for cooling

the water used in the water cooled condenser and some installations use treated water for the ice

making inlet water.

A separate drain will be required for the outlet of the water cooled condenser.

E. Provide a suitable trapped open drain as close as possible to the area where the ice maker is going to

be installed. This may be an existing floor or a 1 1/4”trapped open drain. Connect the drain line to

the rear of the unit and run it with a good fall to the open drain. All plumbing must be installed accord-

ing to local codes. The storage bin drains by gravity, and therefore the drain line must maintain a

gradual slope to an open drain and should be insulated.

NOTE:

IN SOME CASES IT MAY BE NECESSARY TO INSULATE THE WATER SUPPLY LINE AND DRAIN

LINE. CONDENSATE DRIPPING TO THE FLOOR CAN CAUSE SERIOUS STAINING OF CARPETS OR

HARDWOODS.

Содержание Enduro 200

Страница 1: ...r other such method as proved effective by test Water pipe connections and fixtures directly connected to a potable water supply shall be sized installed and maintained according to Federal State and...

Страница 2: ...9 DELAY THERMOSTAT 9 COMPRESSOR START RELAY 10 POTENTIAL RELAYS 10 CAPACITORS GENERAL 10 MAINTENANCE 11 SANITIZING AND CLEANING PROCEDURE 12 WATER TREATMENT 12 WINTER STORAGE 13 CLEANING THE CONDENSE...

Страница 3: ...E 7 WIRING DIAGRAM AF 200 P SC R 115 VOLTS 60 HZ 14 FIGURE 8 WIRING DIAGRAM AF 200 P SC 50 R 220 VOLTS 50 HZ 15 FIGURE 9 WIRING DIAGRAM AF525 SC R AND AF725 SC R 115 VOLTS 60 HZ 16 FIGURE 10 WIRING DI...

Страница 4: ...nt The problems of the serviceman and user have been given special attention in the development and engineering of our ice makers If you encounter a problem which is not covered in this manual please...

Страница 5: ...130 lbs 59 kgs 117 lbs 53 kgs AF 200 P SC50R PRODUCTION CHART AIR TEMPERATURE WATER TEMPERATURE 50 F 10 C 70 F 21 C 80 F 27 C 50 F 10 C 234 lbs 106 kgs 206 lbs 94 kgs 197 lbs 90 kgs 70 F 21 C 213 lbs...

Страница 6: ...0 F 27 C 50 F 10 C 654 lbs 297 kgs 588 lbs 267 kgs 552 lbs 251 kgs 70 F 21 C 639 lbs 290 kgs 563 lbs 256 kgs 521 lbs 237 kgs 90 F 27 C 562 lbs 255 kgs 479 lbs 218 kgs 448 lbs 204 kgs AF 525 P SC50R PR...

Страница 7: ...5 1 32 IN 13 CM 32 1 16 IN 81 CM 4 IN 10 CM FIGURE 3 725 SERIES SPECIFICATIONS ICE PRODUCTION CAPACITY approximate AF 725 P SCR PRODUCTION CHART AIR TEMPERATURE WATER TEMPERATURE 50 F 10 C 70 F 21 C 8...

Страница 8: ...iner provided with the unit should be installed on the down stream side of the shut off valve The supply line must be adequately sized to compensate for the lengths of the incoming water run The machi...

Страница 9: ...draw on the entire unit as well as components such as the gearmotor and fan motor J Check refrigerant circuit and all plumbing connections for leaks etc K Check bin thermostat or mechanical shut off...

Страница 10: ...will be reduced in temperature As a result freezing occurs and ice forms on the surface of the evaporator As more water is frozen the thickness of the ice increases until it exceeds the distance allo...

Страница 11: ...f cool air across it which removes much of the heat from the hot refrigerant vapor As the vapor passing through the condenser loses heat it condenses back to a liquid since it is still under high pres...

Страница 12: ...ng power to the machine HIGH PRESSURE CONTROL Switch contact will open at 450 PSI for R404a breaking the circuit to the compressor This control is manually resetable GEARMOTOR START RELAY This is a cu...

Страница 13: ...1 2 times the supply voltage This voltage sets up a magnetic field which causes the relay to operate The starting relay is calibrated to remove the start capacitor open the start ing circuit at approx...

Страница 14: ...k If the Helix auger on the corkscrew auger round bar becomes flat on the inside more than 1 8 of an inch over a length of two inches or more it should be replaced NOTE HELIX AUGERS DO HAVE MACHINED F...

Страница 15: ...lution and allow them to soak for 10 minutes 9 Using a clean cloth and the sanitizing solution wipe down the interior of the ice chute thermowell door tracks ice bin top and around bin opening Allow t...

Страница 16: ...ch com pressed air hose Start machine As head pressure reaches the appropriate level opening the water regulating valve the compressed air will force the water out Do not let the machine operate longe...

Страница 17: ...165 VAC RD RD BK 4 3 2 WH BK START RELAY GEAR MOTOR FAN SWITCH C O 205 C I 275 GR BK BIN BL BL HIGH PRESS CNTRL C O 450 PSIG MANUAL RESET THERMOSTAT 2 1 3 YL 5 RD R S C COMPRESSOR 1 BK BK OVERLOAD COM...

Страница 18: ...BL 3 4 2 BL START RELAY GEAR MOTOR FAN SWITCH C O 205 C I 275 BR LB GN Y BIN BL BL HIGH PRESS CNTRL C O 450 PSIG MANUAL RESET THERMOSTAT 2 M RD 1 S YL R C BK S COMPRESSOR GN Y 1 BK RD OVERLOAD COMPRE...

Страница 19: ...THERMOSTAT DELAY BL RD START RELAY GEAR MOTOR FAN SWITCH C I 275 C O 205 WH GW BL BIN BL RD CONTROL THERMOSTAT R YL S COMPRESSOR C 1 5 2 1 BK BL BK OVERLOAD COMPRESSOR POTENTIAL START RELAY RD BL BL R...

Страница 20: ...CITOR GEAR MOTOR RD RD BK 3 2 BK BL THERMOSTAT DELAY BK RD START RELAY GEAR MOTOR FAN SWITCH BK GW BIN RD YL BL CONTROL THERMOSTAT RD R C YL GW S 1 COMPRESSOR BK RD RD CONTACTOR COMPRESSOR OVERLOAD BL...

Страница 21: ...or starting capacitor E Check and replace F Loose electrical connection F Check wiring MAKING WET ICE A Surrounding air temperature too high A Correct or move unit B High water level in float reservoi...

Страница 22: ...ath of ice B Adjust thermowell UNIT OFF ON RESET A Ice jams up in evaporator shell A Clean inside surface of evaporator shell B Bin thermostat will not shut off machine Set too cold B Check and adjust...

Страница 23: ...aces causing thicker flaked ice to be made L Replace auger M Auger out of line causing excessive wear on the lower outside surface where it rubs against evaporator shell liner at the bottom M Replace...

Страница 24: ...21 166240010 ILLUSTRATED PARTS BREAKDOWN SERIES 525 725 1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 FIGURE 11 PARTS BREAKDOWN...

Страница 25: ...5V 60HZ 161627001 161627001 161627001 Relay Gearmotor Start Von Weiss 220V 50HZ 161627002 161627002 21 Control High Pressure 165677006 165677006 165677006 22 Control Fan Switch 165677005 165677005 165...

Страница 26: ...20 09120 09120 36555 2 Door Track LH 25007 25007 25007 25007 25007 3 Door Track RH 08824 08824 08824 08824 08824 4 Door Trim 09112 09112 09112 09112 08681 5 Back Panel 163278001 25043 N A N A N A 6 Fr...

Страница 27: ...the ice machine normal prescribed maintenance cleaning adjustments and ice purchases are the responsibility of the original owner No parts warranty or labor allowance on the motor compressor assembly...

Страница 28: ...One Cornelius Place Anoka Minnesota 55303 6234 763 421 6120 800 238 3600 Corporate Headquarters IMI CORNELIUS INC...

Отзывы: