Electrical specifications
Max Gain
1.6 dBi
Impedance
50Ω
Polarization
Vertical
Radiation
Omni
Mechanical
specifications
Connector
Regular SMA-Male
Table 42
– Product Specifications
9.2. PROFINET Specifications
Parameter
Value
Connection 1
“Exclusive Owner - 32 bytes per IO-Link
Port with
Config”
Input data: 276 bytes, Output data: 276 bytes
Connection 2
“Exclusive Owner - 32 bytes per IO-Link
Port without
Config”
Connection 3
“Listen Only - 32 bytes per IO-Link”
Input data: 276 bytes, output data: 0 bytes
Connection 4
“Input Only - 32 bytes per IO-Link”
Connection 5
“Exclusive Owner - 16 bytes per IO-Link
Port without
Config”
Input data: 292 bytes, Output data: 292 bytes
Connection 6
“Listen Only - 16 bytes per IO-Link”
Input data: 292 bytes, output data: 0 bytes
Connection 7
“Input Only - 16 bytes per IO-Link”
Connection 8
“Exclusive Owner - 4 bytes per IO-Link
Port without
Config”
Input data: 100 bytes, Output data: 100 bytes
Connection 9
“Listen Only - 4 bytes per IO-Link”
Input data: 100 bytes, output data: 0 bytes
Connection 10
“Input Only - 4 bytes per IO-Link”
I/O connection types (implicit)
Exclusive ownerOwner Input Only
Listen Only
I/O connection trigger type
Cyclic
Maximum number of I/O connections (class 1)
3
Maximum number of message connections (class 3)
6